Start-up and control with I/O

What this chapter contains

The chapter tells how to:
• perform the start-up
• start, stop, change the direction of the motor rotation and adjust the speed of the
motor through the I/O interface
Using the control panel to do these tasks is explained briefly in this chapter. For
details on how to use the control panel, refer to chapter

How to start up the drive

WARNING! The start-up may only be carried out by a qualified
electrician.
The safety instructions given in chapter
the start-up procedure.
The drive will start up automatically at power up if the external run command is on
and the drive is in the remote control mode.
Check that the starting of the motor does not cause any danger. De-couple the
driven machine if there is a risk of damage in case of incorrect direction of rotation.
Note: By default, parameter
and you cannot see all actual signals and parameters. To be able to view them, set
parameter 1611 PARAMETER VIEW to 3 (LONG VIEW).