Safety In Installation And Maintenance; Electrical Safety - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

16 Safety

Safety in installation and maintenance

These warnings are intended for all who work on the drive, motor cable or motor.

Electrical safety

WARNING! Ignoring the following instructions can cause physical injury or
death, or damage to the equipment.
Only qualified electricians are allowed to install and maintain the drive!
• Never work on the drive, motor cable or motor when input power is applied. After
disconnecting the input power, always wait for 5 minutes to let the intermediate
circuit capacitors discharge before you start working on the drive, motor or motor
cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm) that
there is no voltage between the drive input phases U1, V1 and W1 and the
ground.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may carry dangerous
voltage even when the input power of the drive is switched off.
• Do not make any insulation or voltage withstand tests on the drive.
• If a drive whose EMC filter is not disconnected is installed on an IT system (an
ungrounded power system or a high resistance-grounded [over 30 ohms] power
system), the system will be connected to ground potential through the EMC filter
capacitors of the drive. This may cause danger or damage the drive.
• If a drive whose EMC filter is not disconnected is installed on a corner grounded
TN system, the drive will be damaged.
• All ELV (extra low voltage) circuits connected to the drive must be used within a
zone of equipotential bonding, ie within a zone where all simultaneously
accessible conductive parts are electrically connected to prevent hazardous
voltages appearing between them. This is accomplished by a proper factory
grounding.
Note:
• Even when the motor is stopped, dangerous voltage is present at the power
circuit terminals U1, V1, W1 and U2, V2, W2.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents