Settings; Diagnostics - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

When the speed regulated motor reaches the full output, it is disconnected from the
drive and switched to direct on-line connection, with a slight delay in between.
Auxiliary motor 2 is connected to drive output. After a slight delay the motor speed is
increased to fulfil the pumping capacity needed.
Auxiliary motors 3 and 4 are started according to the same routine.
The motor stopping routine follows always the normal PFC routine.
The most important differences between PFC control and SPFC control default
settings are in acceleration time (2202), deceleration time (2203) and auxiliary motor
stop delay (8116) parameters.
See also section
SPFC Control macro

Settings

Parameter
Group
14 RELAY OUTPUTS
Group
44 PUMP PROTECTION
Group
81 PFC CONTROL

Diagnostics

Actual signal
0116
0162
0173
Alarm
AUTOCHANGE
PFC I LOCK
INLET
LOW,
INLET VERY LOW
OUTLET
HIGH,
OUTLET VERY
HIGH
Fault
PAR PFC REF NEG
PAR PFC IO 1
PAR PFC IO 2
PAR PFC IO 3
INLET
LOW,
INLET VERY LOW
OUTLET
HIGH,
OUTLET VERY
HIGH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
on page 109.
Additional information
Selections of relay outputs for starting and stopping of
motors
Pump protection (pressure monitoring) settings
PFC control settings
Additional information
Application block output signal
RO 1 status
RO 2...4 status. With option MREL-01 only.
PFC Autochange function active
PFC interlocks active
Pressure at pump/fan inlet too low
Pressure at pump/fan outlet too high
Additional information
< 0
2007
Not enough relays parameterized for PFC.
Conflict between group
parameter
and parameter 8118.
8117
Parameter
does not match the PFC motors in
8127
group
14 RELAY OUTPUTS
Allocation of a digital input (interlock) for each PFC
motor not possible
Pressure at pump/fan inlet too low
Pressure at pump/fan outlet too high
Program features 147
14 RELAY
OUTPUTS,
and parameter
8118