Power Connections And Control Interfaces - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

Power connections and control interfaces

The diagram gives an overview of connections. I/O connections are parameterable.
See chapter
Application macros
macros and chapter
Screen
Analog input 1
0...10 V
Reference voltage
+10 V DC, max. 10 mA
Analog input 2
Aux. voltage output
+24 V DC, max. 200 mA
PROGRAMMABLE
DIGITAL INPUTS
DI5 can also be used
as a frequency input
Modbus RTU
(RS-485)
FlashDrop
3-phase power
supply,
200...480 V AC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Operation principle and hardware description 25
on page
Electrical installation
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
9
+24 V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
23
SHIELD
24
J701
B
25
A
26
GND_A
6
PE
L1
U1
L2
V1
L3
W1
for I/O connections for the different
99
on page
for installation in general.
45
8
S1
AO 7
GND 8
mA
V
ROCOM
17
RONC
18
RONO
19
DOSRC
20
DOOUT
21
DOGND
22
EMC
VAR
U2
V2
W2
Control panel
(RJ-45)
Modbus RTU
(RS-232)
Analog output
0...20 mA
PROGRAMMABLE RELAY
AND DIGITAL OUTPUTS
Relay output
250 V AC / 30 V DC / 6 A
Digital/frequency output,
PNP transistor type
30 V DC, max. 100 mA
6
Output relay
module MREL-01
EMC filter grounding screw
Varistor grounding screw
M
AC motor
3 ~

Hide quick links:

Advertisement

Table of Contents