A parameter which is triggered by a timed function can be connected to only one
timed function at a time.
TIMED FUNC 1
3626 TIMED FUNC 1 SRC
TIMED FUNC 2
3627 TIMED FUNC 2 SRC

Example

Air conditioning is active on weekdays from 8:00 to 15:30 (8 a.m to 3:30 p.m) and on
Sundays from 12:00 to 15:00 (12 to 3 p.m). By pressing the extension time switch,
the air-conditioning is on for an extra hour.
Parameter
START TIME 1
3602
STOP TIME 1
3603
START DAY 1
3604
STOP DAY 1
3605
START TIME 2
3606
STOP TIME 2
3607
START DAY 2
3608
STOP DAY 2
3609
BOOSTER TIME
3623

Settings

Parameter
36 TIMED FUNCTIONS
1001,
1002
1102
1201
1209
1401
1402/1403/1410
1805
4027
4228
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting
08:00:00
15:30:00
MONDAY
FRIDAY
12:00:00
15:00:00
SUNDAY
SUNDAY
01:00:00
Additional information
Timed functions settings
Timed start/stop control
Timed EXT1/EXT2 selection
Timed constant speed 1 activation
Timed speed selection
Timed function status indicated through relay output RO 1
Timed function status indicated through relay output RO 2...4.
With option MREL-01 only.
Timed function status indicated through digital output DO
Timed PID1 parameter set 1/2 selection
Timed external PID2 activation
1001 EXT 1 COMMANDS
1002 EXT 2 COMMANDS
1102 EXT1/EXT2 SE
1201 CONST SPEED SEL
1209 TIME MODE SEL
1401 RELAY OUTPUT 1
4027 PID PARAM SET
4228 ACTIVATE