Motor Potentiometer Macro; Default I/O Connections - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

Motor Potentiometer macro

This macro provides a cost-effective interface for PLCs that vary the speed of the
motor using only digital signals. To enable the macro, set the value of parameter
APPLIC MACRO to 4 (MOTOR POT).
For the parameter default values, see section
page 151. If you use other than the default connections presented below, see section
on page 49.
I/O terminals

Default I/O connections

max. 500 ohm
1)
If DI3 and DI4 are both active or inactive, the
speed reference is unchanged.
The existing speed reference is stored
during stop and power down.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Not in use by default. 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Motor speed value: 0...20 mA
8
GND
Analog output circuit common
2)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Forward (0) / Reverse (1)
14 DI3
Speed reference up
15 DI4
Speed reference down
16 DI5
Constant speed 1: parameter
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
Application macros 105
Default values with different macros
1)
1)
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
Tightening torque = 0.4 N·m / 3.5 lbf in.
9902
on
1202

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents