Maintenance Trig - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

All parameters
No.
Name/Value
2618 FW VOLTAGE
0...120% of U
N
2619 DC
STABILIZER
DISABLE
ENABLE
29 MAINTENANCE
TRIG
2901 COOLING FAN
TRIG
0.0...6553.5 kh Time. If parameter value is set to zero, the trigger is
2902 COOLING FAN
ACT
0.0...6553.5 kh Time. Parameter is reset by setting it to zero.
2903 REVOLUTION
TRIG
0...65535 Mrev Millions of revolutions. If parameter value is set to zero, the
2904 REVOLUTION
ACT
0...65535 Mrev Millions of revolutions. Parameter is reset by setting it to
2905 RUN TIME
TRIG
0.0...6553.5 kh Time. If parameter value is set to zero, the trigger is
2906 RUN TIME
ACT
0.0...6553.5 kh Time. Parameter is reset by setting it to zero.
2907 USER MWh
TRIG
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Defines the voltage of the U/f curve when frequency is equal
to or exceeds the motor nominal frequency
NOM FREQ). See section
V Voltage
Enables or disables the DC voltage stabilizer. The DC
stabilizer is used to prevent possible voltage oscillations in
the drive DC bus caused by motor load or weak supply
network. In case of voltage variation, the drive tunes the
frequency reference to stabilize the DC bus voltage and
therefore the load torque oscillation.
Disabled
Enabled
Maintenance triggers
Defines the trigger point for the drive cooling fan run time
counter. Value is compared to parameter
FAN ACT value.
disabled.
Defines the actual value for the cooling fan run time counter.
When parameter
2901
to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by
parameter 2901, a maintenance notice is displayed on the
panel.
Defines the trigger point for the motor revolution counter.
Value is compared to parameter
value.
trigger is disabled.
Defines the actual value for the motor revolution counter.
When parameter
2903
a non zero value, the counter starts. When the actual value
of the counter exceeds the value defined by parameter
2903, a maintenance notice is displayed on the panel.
zero.
Defines the trigger point for the drive run time counter. Value
is compared to parameter
disabled.
Defines the actual value for the drive run time counter.
When parameter
2905
non zero value, the counter starts. When the actual value of
the counter exceeds the value defined by parameter 2905, a
maintenance notice is displayed on the panel.
Defines the trigger point for the drive power consumption
counter. Value is compared to parameter
ACT value.
Actual signals and parameters 193
Custom U/f ratio
2902
COOLING FAN TRIG has been set
REVOLUTION ACT
2904
REVOLUTION TRIG has been set to
RUN TIME ACT value.
2906
RUN TIME TRIG has been set to a
2908
Def/FbEq
95% of
(9907
MOTOR
U
N
on page 128.
1 = 1 V
DISABLE
0
1
0.0 kh
COOLING
1 = 0.1 kh
0.0 kh
1 = 0.1 kh
0 Mrev
1 = 1
Mrev
0 Mrev
1 = 1
Mrev
0.0 kh
1 = 0.1 kh
0.0 kh
1 = 0.1 kh
0.0 MWh
USER MWh