Dc Magnetizing; Settings; Maintenance Trigger; Acceleration And Deceleration Ramps - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

126 Program features

DC Magnetizing

When DC Magnetizing is activated, the drive automatically magnetizes the motor
before starting. This feature guarantees the highest possible breakaway torque, up to
180% of the motor nominal torque. By adjusting the paramagnetism time, it is
possible to synchronize the motor start. The Automatic Start feature and DC
Magnetizing cannot be activated at the same time.

Settings

Parameters
START FUNCTION and
2101

Maintenance trigger

A maintenance trigger can be activated to show a notice on the panel display when
eg drive power consumption has exceeded the defined trigger point.

Settings

Parameter group
29 MAINTENANCE TRIG

Acceleration and deceleration ramps

Two user-selectable acceleration and
deceleration ramps are available. It is possible to
adjust the acceleration/deceleration times and
the ramp shape. Switching between the two
ramps can be controlled via a digital input or
fieldbus.
The available ramp shape alternatives are
Linear and S-curve.
Linear: Suitable for drives requiring steady or
slow acceleration/deceleration.
S-curve: Ideal for conveyors carrying fragile loads, or other applications where a
smooth transition is required when changing the speed.

Settings

Parameter group
22 ACCEL/DECEL
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
DC MAGN TIME
2103
Motor speed
Linear
S-curve
t (s)
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents