Electric Power Network Specification; Motor Connection Data - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

314 Technical data

Electric power network specification

Voltage (U
)
1
Short-circuit capacity
Frequency
Imbalance

Motor connection data

Voltage (U
)
2
Short-circuit protection
(IEC 61800-5-1,
UL 508C)
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum
recommended
motor cable length
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
200/208/220/230/240 V AC 3-phase for 200 V AC drives
380/400/415/440/460/480 V AC 3-phase for 400 V AC drives
±10% variation from converter nominal voltage is allowed as default.
Maximum allowed prospective short-circuit current at the input power
connection as defined in IEC 60439-1 is 100 kA. The drive is suitable
for use in a circuit capable of delivering not more than 100 kA rms
symmetrical amperes at the drive maximum rated voltage.
50/60 Hz ± 5%, maximum rate of change 17%/s
Max. ±3% of nominal phase to phase input voltage
0 to U
, 3-phase symmetrical, U
1
The motor output is short-circuit proof by IEC 61800-5-1 and
UL 508C.
0...500 Hz
0.01 Hz
See section
Ratings
1.5 · P
N
10...500 Hz
4, 8, 12 or 16 kHz
R0: 30 m (100 ft), R1...R4: 50 m (165 ft)
With output chokes the motor cable length may be extended to 60 m
(195 ft) for R0 and 100 m (330 ft) for R1...R4.
To comply with the European EMC Directive, use the cable lengths
specified in the table below for 4 kHz switching frequency. The
lengths are given for using the drive with the internal EMC filter or an
optional external EMC filter.
4 kHz switching
frequency
Second environment
1)
(category C3
)
First environment
1)
(category C2
)
1)
See the new terms in section
at the field weakening point
max
on page 308.
Internal EMC filter
30 m (100 ft)
-
Definitions
Optional external
EMC filter
30 m (100 ft)
minimum
30 m (100 ft)