40 Planning the electrical installation
A diagram of the cable routing is shown below.
Input power cable
min. 200 mm (8 in)
Control cable ducts
24 V
Not allowed unless the 24 V cable is
insulated for 230 V or insulated with an
insulation sleeving for 230 V.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Drive
90°
Control cables
230 V
Motor cable
Power cable
Motor cable
min. 500 mm (20 in)
24 V
Lead 24 V and 230 V control cables in
separate ducts inside the cabinet.
min. 300 mm (12 in)
230 V