Embedded Fieldbus Faults; No Master Device; Same Device Address; Incorrect Wiring - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

CODE FAULT
1012
PAR PFC IO 1
(6320)
bit 15
0307
1013
PAR PFC IO 2
(6320)
bit 15
0307
1014
PAR PFC IO 3
(6320)
bit 15
0307
1015
PAR CUSTOM U/F
(6320)
bit 15
0307
1017
PAR SETUP 1
(6320)
bit 15
0307
1026
PAR USER LOAD C
(6320)
bit 15
0307
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CAUSE
I/O configuration for
PFC not complete
I/O configuration for
PFC not complete
I/O configuration for
PFC not complete.
The drive is unable to
allocate a digital input
(interlock) for each
PFC motor.
Incorrect voltage to
frequency
(U/f) ratio voltage
setting.
It is not allowed to use
frequency input signal
and frequency output
signal simultaneously.
Incorrect user load
curve parameter
setting
Fault tracing 301
WHAT TO DO
Check parameter settings. Following
must apply:
• There are enough relays
parameterized for PFC.
• No conflict exists between
parameter group
14 RELAY
OUTPUTS, parameter
AUX MOT and parameter
AUTOCHNG INTERV.
Check parameter settings. Following
must apply:
• The actual number of PFC motors
(parameter
MOTORS)
8127
matches the PFC motors in
parameter group
14 RELAY
and parameter
OUTPUTS
AUTOCHNG INTERV.
See parameters
8120
and
MOTORS.
8127
Check parameter
2610
DEFINED
U1...2617
F4 settings.
Disable frequency output or frequency
input:
• change transistor output to digital
mode (value of parameter
MODE = DIGITAL), or
• change frequency input selection to
other value in parameter groups
11 REFERENCE SELECT,
40 PROCESS PID SET 1,
41 PROCESS PID SET 2
42 EXT / TRIM
PID.
Check parameter settings. Following
must apply:
LOAD FREQ 1 <
3704
LOAD FREQ 2 <
3707
LOAD FREQ 3 <
3710
LOAD FREQ 4 <
3713
LOAD FREQ 5
3716
LOAD TORQ LOW 1 <
3705
LOAD TORQ HIGH 1
3706
LOAD TORQ LOW 2 <
3708
LOAD TORQ HIGH 2
3709
LOAD TORQ LOW 3 <
3711
LOAD TORQ HIGH 3
3712
LOAD TORQ LOW 4 <
3714
LOAD TORQ HIGH 4
3715
LOAD TORQ LOW 5 <
3717
LOAD TORQ HIGH 5.
3718
NR OF
8117
8118
8118
INTERLOCKS
USER
USER DEFINED
TO
1804
and

Hide quick links: