System Controls - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

All parameters
No.
Name/Value
1502 AO1
CONTENT MIN
x...x
1503 AO1
CONTENT
MAX
x...x
1504 MINIMUM AO1 Defines the minimum value for the analog output signal AO.
0.0...20.0 mA
1505 MAXIMUM
AO1
0.0...20.0 mA
1506 FILTER AO1
0.0...10.0 s
16 SYSTEM
CONTROLS
1601 RUN ENABLE
NOT SEL
DI1
DI2
DI3
DI4
DI5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Defines the minimum value for signal selected with
parameter
AO1 CONTENT SEL.
1501
AO minimum and maximum correspond the
AO1 and
MAXIMUM AO1 settings as follows:
1505
AO (mA)
1505
1504
1502
1503
Setting range depends on parameter
SEL setting.
Defines the maximum value for signal selected with
parameter
AO1 CONTENT SEL. See the figure for
1501
parameter
AO1 CONTENT MIN.
1502
Setting range depends on parameter
SEL setting.
See the figure for parameter
Minimum value
Defines the maximum value for the analog output signal AO.
See the figure for parameter
Maximum value
Defines the filter time constant for analog output AO, ie the
time within 63% of a step change is reached. See the figure
for parameter
FILTER AI1.
1303
Filter time constant
Parameter view, Run Enable, parameter lock etc.
Selects a source for the external Run Enable signal.
Allows the drive to start without an external Run Enable
signal.
External signal required through digital input DI1. 1 = Run
Enable. If Run Enable signal is switched off, the drive will
not start or coasts to stop if it is running.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Actual signals and parameters 175
1504
AO (mA)
1505
1504
1503
AO
content
AO1 CONTENT
1501
AO1 CONTENT
1501
AO1 CONTENT MIN.
1502
AO1 CONTENT MIN.
1502
Def/FbEq
-
MINIMUM
1502
AO
content
-
-
-
0.0 mA
1 = 0.1
mA
20.0 mA
1 = 0.1
mA
0.1 s
1 = 0.1 s
NOT SEL
0
1
2
3
4
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents