54 Electrical installation
Connecting the embedded fieldbus
Embedded fieldbus can be connected to the drive with RS-485 or RS-232.
Connection diagram
RS-485
The figure below shows the fieldbus connection.
X1C
23 SCR
SCR
+
24 B
-
25 A
GND
25 GND_A Fieldbus common
Terminate the RS-485 bus with a 120 ohm resistor at the end of the network by
setting the jumper J701 shunts as in the figure below.
Jumper shunts
connect the
120 ohm
termination
resistor.
RS-232
Plug a communication cable into the control panel connection X2. The cable must be
shorter than 3 meters.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Fieldbus cable shield (screen)
Positive
Negative
J701
J701
J701
SCR
RS-484
Fieldbus
J701
Fieldbus
controller
RS-232
< 3 m
B
A
GND_A
X1C
Fieldbus
controller