Noise; Terminal And Lead-Through Data For The Power Cables; Terminal And Lead-Through Data For The Control Cables - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

Noise

Frame
Noise level
dBA
size
R0
<30
R1
50...62
R2
50...62
R3
50...62
R4
<62
00578903.xls D

Terminal and lead-through data for the power cables

Frame
Max. cable
diameter for
size
NEMA 1
U1, V1, W1,
U2, V2, W2
mm
R0
16
0.63
R1
16
0.63
R2
16
0.63
R3
29
1.14
R4
35
1.38

Terminal and lead-through data for the control cables

Solid or stranded
Min/Max
Min/Max
2
mm
AWG
0.14/1.5
26/16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
U1, V1, W1, U2, V2, W2
Max. terminal size
flexible/rigid
2
in
mm
AWG
4.0/6.0
10
4.0/6.0
10
4.0/6.0
10
10.0/16.0
25.0/35.0
Conductor size
Stranded, with ferrule
without plastic sleeve
Min/Max
2
mm
0.25/1.5
Tightening
torque
N·m
lbf·in
0.8
7
0.8
7
0.8
7
6
1.7
15
2
2.5
22
Stranded, with ferrule
with plastic sleeve
Min/Max
Min/Max
AWG
mm
23/16
0.25/1.5
Technical data 313
PE
Max. clamp size
Tightening
solid or stranded
2
mm
AWG
N·m lbf·in
25
3
25
3
25
3
25
3
25
3
00578903.xls D
Tightening
Min/Max
2
AWG
N·m lbf·in
23/16
torque
1.2
11
1.2
11
1.2
11
1.2
11
1.2
11
torque
0.4
3.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents