Timed Functions - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

All parameters
No.
Name/Value
DI5
3503 ALARM LIMIT
x...x
3504 FAULT LIMIT
x...x
3505 AO
EXCITATION
DISABLE
ENABLE
36 TIMED
FUNCTIONS
3601 TIMERS
ENABLE
NOT SEL
DI1
DI2
DI3
DI4
DI5
ACTIVE
DI1 CMODE
DI2 CMODE
DI3 CMODE
DI4 CMODE
DI5 CMODE
CONT MODE
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Digital input DI5. Used when parameter
TYPE value is set to THERMI(0)/(1).
Defines the alarm limit for motor temperature measurement.
Alarm MOTOR TEMP indication is given when the limit is
exceeded. When parameter
set to THERMI(0)/(1): 1 = alarm.
Alarm limit
Defines the fault trip limit for motor temperature
measurement. The drive trips on fault MOT OVERTEMP
when the limit is exceeded. When parameter
SENSOR TYPE value is set to THERMI(0)/(1): 1 = fault.
Fault limit
Enables current feed from analog output AO. Parameter
setting overrides parameter group
settings.
With PTC the output current is 1.6 mA.
With Pt 100 the output current is 9.1 mA.
Disabled
Enabled
Time periods 1 to 4 and booster signal. See section
on page 141.
functions
Selects the source for the timed function enable signal.
Timed function is not selected.
Digital input DI. Timed function enable on the rising edge of
DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Timed function is always enabled.
Timed function enable on the rising edge of DI1. Timed
function is in continuous mode, in which the start date can
be different from the stop date.
See selection DI1 CMODE.
See selection DI1 CMODE.
See selection DI1 CMODE.
See selection DI1 CMODE.
Timed function enabled in continuous mode, in which the
start date can be different from the stop date.
Inverted digital input DI1. Timed function enable on the
falling edge of DI1.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Actual signals and parameters 209
SENSOR
3501
SENSOR TYPE value is
3501
3501
15 ANALOG OUTPUTS
Def/FbEq
7
0
-
0
-
DISABLE
0
1
Timed
NOT SEL
0
1
2
3
4
5
7
11
12
13
14
15
17
-1
-2
-3
-4
-5