Running hour-meter TEILGAPC

Identification

Function Description
Running hour-meter

Application

The function is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is to accumulate the total
running/energized time of the generator, transformer, reactor, capacitor bank or
even line.
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 99999.9 hours. At overflow the accumulated time
resets and the accumulation starts from zero again.

Setting guidelines

The settings tAlarm and tWarning are user settable limits defined in hours. The
achievable resolution of the settings is 0.1 hours (6 minutes).
tAlarm and tWarning are independent settings, that is, there is no
check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting tAddToTime is a user settable time parameter in hours.
IEC 61850
IEC 60617
identification
identification
TEILGAPC
-
Section 16
Monitoring
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
ANSI/IEEE C37.2 device
number
-
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
279