Boolean To Integer Conversion With Logical Node Representation, 16 Bit Btigapc; Identification; Application - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 15
Logic
15.9
15.9.1
15.9.2
240
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC

Identification

Function description
Boolean to integer conversion with
logical node representation, 16 bit

Application

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC)
is used to transform a set of 16 binary (logical) signals into an integer. BTIGAPC
has a logical node mapping in IEC 61850.
The BTIGAPC function will transfer a combination of up to 16 binary inputs INx
where 1≤x≤16 to an integer. Each INx represents a value according to the table
below from 0 to 32768. This follows the general formula: INx = 2
1≤x≤16. The sum of all the values on the activated INx will be available on the
output OUT as a sum of the values of all the inputs INx that are activated. OUT is
an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it
corresponds to that integer 65535 is available on the output OUT. BTIGAPC
function is designed for receiving up to 16 booleans input locally. If the BLOCK
input is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the
output OUT on the function block BTIGAPC.
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
Table continues on next page
IEC 61850
IEC 60617
identification
identification
BTIGAPC
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
Phasor measurement unit RES670 2.2 IEC
1MRK 511 407-UEN C
SEMOD175753-1 v4
SEMOD175757-2 v5
ANSI/IEEE C37.2
device number
-
-
SEMOD175849-4 v6
x-1
where
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
Application manual