Basic Unit; Time Parameters; Figure 5: Example: 1-/2-Stage Oil Burner - Siemens LMO39 Series Basic Documentation

Burner controls
Table of Contents

Advertisement

LMO39...
Building Technologies
3

Basic unit

The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It
is of plug-in design and engages audibly in the base
Burner controls LMO39... and plug-in base AGK11.6 are silver-grey (RAL7001)
The housing accommodates the
microcontroller for the program control and the control relays for load control
electronic flame signal amplifier
– lockout reset button with its integrated 3-color signal lamp for operational status
and fault status messages and the socket for connecting the interface OCI400...
adapter or the AGK20... lockout reset button extension
All safety-related digital inputs and outputs of the system are monitored by means
of a contact feedback network
The display and operating unit AZL2... is designed for direct connection to the
LMO39...
The LMO39... is operated and parameterized via the AZL2... or with the help of the
OCI410 / ACS410
Burner capacity unlimited (thermal output on startup '120 kW)
3 repetitions in the event of loss of flame during operation (can be parameterized)
 Default setting: Non-alterable lockout

Figure 5: Example: 1-/2-stage oil burner

The diagram shows the full scope of functions of the LMO39... system. The actual
functions are to be determined based on the respective execution/configuration.

3.1 Time parameters

Parameterized times see Type summary.
Both the prepurge time and the safety times are safety-related and can be changed by
the OEM with the help of the display and operating unit AZL2... or PC software
ACS410.
Basic Documentation LMO39...
3 Basic unit
:
13/61
CC1P7154en
15.03.2018