4.22 Additional pump Q17 for heat pump stage 2
(ZuFu5)
• Control of an additional circulating pump with 2-stage heat pumps
With 2-stage heat pumps (2 compressors and 2 condensers), an additional circulating
pump can be used for drawing heat off the second condenser.
For the control of the second heat pump stage and the additional pump, the controller
uses the same sensor values as with the first heat pump stage. Hence, the second
pump must hydraulically be integrated such that the sensors (B21 and / or B71) are lo-
cated in the section where there is flow (refer to application example).
Setting range
--- / 101...110
The auxiliary function is activated as soon as relay Q17 is assigned a free terminal:
101...110
The relay for the second circulating pump Q17 can be assigned to a
free relay terminal between Q101 and Q110.
---
No assignment made and the auxiliary function is not activated.
For the pump pre- and overrun (operating lines 410
ters are used as with heat pump stage 1.
An additional pump for the second heat pump stage Q17 can be integrated in the plant
diagram as follows:
Example:
Wp 4
Q8
B21
K2
K1
Q9
B11
B71
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
Q17
EXP
ZuFu 5
Q17
Factory setting
---
and 411
), the same parame-
EXP
CE1P2488en