Gas Direct Ignition (G), 1-Stage, With Valve Proving; Gas Direct Ignition (G), 2-Stage, With Valve Proving - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

LME73.000...
X7-02
LME73.000...
X7-01
X7-02
X7-04
Building Technologies
HVAC Products

13.2.3 Gas direct ignition (G), 1-stage, with valve proving

Program
X7-04
SV
Figure 29: Connection diagram fuel train gas direct ignition (G), 1-stage, with valve proving

13.2.4 Gas direct ignition (G), 2-stage, with valve proving

Program
SV
Figure 30: Connection diagram fuel train gas direct ignition (G), 2-stage, with valve proving
Note:
When valve proving is activated (e.g. on shutdown), the load on the valve's
terminals (according to Technical data / Terminal rating Outputs) is re-
stricted.
Fuel valve 1 (V1) X7-04/4 / (V2) X7-02/3 / auxiliary output AUX
If the terminal load (according to Technical data / Terminal rating Outputs) is
not reduced (max. rated current 2 A, cosϕ >0.4), the design life time will be
reached after about 100,000 burner startup cycles!
Basisdokumentation LME7...
13 PME73.810...
G
Gas direct 2-stage, with valve proving
G
V1
Rated voltage
AC 120 V
50 / 60 Hz
Rated current
1 A
Power factor
cosϕ >0.4
Gas direct 1-stage, with valve proving
V1
V2
V2
V2a
AC 230 V
50 / 60 Hz
1 A
cosϕ >0.4
47/164
CC1P7105de
24.09.2009