Figure 5-2. Powerware Hot Sync Can Bridge Card Connections - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

Table 5‐1. Powerware Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Figure 5‐2. Powerware Hot Sync CAN Bridge Card Connections
Name
Description
1
Alarm
Programmable UPS alarm. Activated by a remote dry contact closure.
2
Alarm Return
3
Alarm Relay NC
Normally‐closed contact opens when UPS is on bypass.
4
Alarm Relay Com
Bypass contact return.
5
Alarm Relay NO
Normally‐open contact closes when UPS is on bypass.
6
TX
RMP II, RIM II, and SCM II connections.
7
TX
8
CAN L
9
Can H
CAN input for parallel operation.
10
Shield
INSTALLING OPTIONS AND ACCESSORIES
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status