■Operation result
1.
Function without EN/ENO
The following table lists the operation results.
Operation result
No operation error occurred
An operation error occurred
2.
Function with EN/ENO
The following table lists the execution conditions and operation results.
Execution condition
EN
TRUE (Executes operation)
FALSE (Stops operation)
*1 When FALSE is output from ENO, data output from (d) is undefined. In that case, modify a program so that the data output from (d) is
not used.
Operation error
Error code
Description
(SD0/SD8067)
2820H
In the corresponding device range of the device specified by (s) and later, "00H" does not exist.
3405H
The character string specified by (s) has more than 16383 characters.
3406H
The whole specified character string cannot be stored in the devices from the device specified by (d) to the last device in the
corresponding device range.
20 ARITHMETIC OPERATION FUNCTIONS
1000
20.7 Move Operation
(d)
Operation output value
Indefinite value
Operation result
ENO
TRUE (Operation error did not occur)
FALSE (Operation error occurred)
*1
FALSE
(d)
Operation output value
*1
Indefinite value
Indefinite value