7 Block BASIC FUNCTION
52
7.4.2

Function group OPERATION

BASIC FUNCTION
G
BASIC FUNCTION
All sensor data (measuring period, overvoltage time, etc.) are set at the factory and saved on the S-DAT (sensor memory
chip).
"
Caution!
Under normal circumstances you should not change the following parameter settings, because changes affect numerous
functions of the entire measuring facility in general and the accuracy of the measuring system in particular. For this
reason, the functions described below cannot be changed even when you enter your private code.
Contact the Endress+Hauser service organization if you have any questions about these functions.
MEASURING PERIOD
Use this function to view the measuring period. The duration of the measuring period is
(6820)
calculated from the rise time of the magnetic field, the brief recovery time, the integration
time and the empty pipe detection time.
User interface:
Max. 4-digit number: 10 to 1000 ms
Factory setting:
Depends on nominal diameter
EPD ELECTRODE
Use this function to check whether the sensor is equipped with an EPD electrode.
(6822)
User interface:
YES
NO
Factory setting:
YES → Electrode fitted as standard
Device Functions Proline Promag 55 FOUNDATION Fieldbus
FOUNDATION FIELDBUS GGA
PROCESS PARAMETER
GIA
SYSTEM PARAMETER
GLA
SENSOR DATA
GNA
Function description
SENSOR DATA
CONFIGURATION
OPERATION
OPERATION
Endress+Hauser
680
682