Device Functions Proline Promag 55 FOUNDATION Fieldbus
Endress+Hauser
7.3

Group SYSTEM PARAMETER

7.3.1

Function group CONFIGURATION

BASIC FUNCTION
G
BASIC FUNCTION
INSTALLATION
Use this function to reverse the sign of the flow measured variable, if necessary.
DIRECTION
SENSOR
Options:
(6600)
NORMAL (flow as indicated by the arrow)
INVERSE (flow opposite to direction indicated by the arrow)
Factory setting:
NORMAL
!
Ascertain the actual direction of fluid flow with reference to the direction indicated by
the arrow on the sensor (nameplate).
SYSTEM DAMPING
Use this function to set the filter depth of the digital filter. This reduces the sensitivity of
(6603)
the measuring signal to interference peaks (e.g. high solids content, gas bubbles in the
fluid, etc.). The reaction time of the measuring system increases with every increase in
the filter setting.
User input:
0 to 15
Factory setting:
7
!
The system damping acts on all functions and outputs of the measuring device.
INTEGRATION TIME
Use this function to view the set integration time.
(6604)
The integration time defines the duration of internal totaling of the induced voltage in the
fluid (measured by the measuring electrode), i.e. the time in which the measuring device
records the true flow (afterwards the magnetic field for the next integration is created
from the opposite pole).
User interface:
Max. 2-digit number: 1 to 65 ms
Factory setting:
5 ms
POSITIVE ZERO RETURN
Use this function to interrupt evaluation of measured variables. This is necessary when a
(6605)
piping system is being cleaned, for example. This setting acts on all function and outputs
of the measuring device.
Options:
OFF
ON → Signal output is set to the "ZERO FLOW" value.
Factory setting:
OFF
FOUNDATION FIELDBUS GGA
PROCESS PARAMETER
GIA
SYSTEM PARAMETER
GLA
Function description
SYSTEM PARAMETER
Note!
Note!
7 Block BASIC FUNCTION
CONFIGURATION
CONFIGURATION
660
49