Device functions Proline Promag 55 FOUNDATION Fieldbus
Endress+Hauser
Write access with
Parameter
operating mode
(MODE_BLK)
1 = Main line
2 = Additional line
3 = Information line
Main Line -
AUTO - OOS
Assign
Main Line -
AUTO - OOS
100% - Value
"Display" Transducer Block/base index 1800:
Esc
+
-
In this parameter, a value to be displayed is assigned to the main line (top
line in the local display). This value is displayed during normal operation.
Options:
OFF
VOLUME FLOW
MASS FLOW
VOLUME FLOW IN %
MASS FLOW IN %
TOTALIZER (1 to 3)
AI1 - OUT VALUE
AI2 - OUT VALUE
AI3 - OUT VALUE
AI4 - OUT VALUE
AI5 - OUT VALUE
PID - IN VALUE (controlled variable)
PID - CAS IN VALUE (external set point)
PID - OUT VALUE (manipulated variable)
Factory setting:
VOLUME FLOW
The entry is not active unless one of the following was selected in the
parameter "Main Line - Assign":
• MASS FLOW IN %
• VOLUME FLOW IN %
Use this function to define the flow value to be shown on the display as
the 100% value.
User input:
5-digit floating-point number
Factory setting:
Nominal diameter and country dependent → Page 123 ff.
!
Note!
The unit is taken from the "System Unit - Volume Flow" or "System Unit -
Mass Flow" parameter ( → Page 79 ff.).
3 Transducer Block
Description
1
2
3
E
A0001253
97