Endress+Hauser Proline Promag 55 Operating Manual

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

Quick Links

Description of Device Functions
Proline Promag 55
FOUNDATION FIELDBUS
Electromagnetic Flow Measuring System
9
BA127D/06/en/09.06
71032705
valid as of version:
V 2.00.XX (Device software)
A
AAA
000
0000
0001
0002
A
AAA
000
0000
0001
0002
020
0200
0201
0202
020
0200
0201
0202
B
BAA
100
1000
1001
1002
B
BAA
100
1000
1001
1002
C
CAA
200
2000
2001
2002
C
CAA
200
2000
2001
2002
220
2200
2201
2202
CBA
220
2200
2201
2202
CBA
CCA
240
2400
2401
2402
240
2400
2401
2402
CCA
D
DAA
300
3000
3001
3002
D
DAA
300
3000
3001
3002
E
EAA
400
4000
4001
4002
400
4000
4001
4002
E
EAA
420
4200
4201
4202
420
4200
4201
4202
F
FAA
500
5000
5001
5002
F
FAA
500
5000
5001
5002
520
5200
5201
5202
520
5200
5201
5202
0003
0004
0005
0003
0004
0005
0203
0204
0205
0203
0204
0205
1003
1004
1005
1003
1004
1005
2003
2004
2005
2003
2004
2005
2203
2204
2205
2203
2204
2205
2403
2404
2405
2403
2404
2405
3003
3004
3005
3003
3004
3005
4003
4004
4005
4003
4004
4005
4203
4204
4205
4203
4204
4205
5003
5004
5003
5004
5203
5203

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promag 55

  • Page 1 Description of Device Functions Proline Promag 55 FOUNDATION FIELDBUS Electromagnetic Flow Measuring System 0000 0001 0002 0003 0004 0005 0000 0001 0002 0003 0004 0005 0200 0201 0202 0203 0204 0205 0200 0201 0202 0203 0204 0205 1000 1001 1002...
  • Page 2 Device Functions Proline Promag 55 FOUNDATION Fieldbus Operating Promag 55 FOUNDATION Fieldbus → Page 3 with local operation: → Page 67 with FOUNDATION Fieldbus: Endress+Hauser...
  • Page 3: Table Of Contents

    Device Functions Proline Promag 55 FOUNDATION Fieldbus Table of contents (local operation) Table of contents (local operation) Using the manual Block BASIC FUNCTION ....
  • Page 4 Table of contents (local operation) Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress+Hauser...
  • Page 5: Using The Manual

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 1 Using the manual Using the manual There are various ways of locating the description of a function of your choice in the manual: Using the table of contents to locate a function description The designations of all the cells in the function matrix are listed in the table of contents.
  • Page 6: Function Matrix

    2 Function matrix Device Functions Proline Promag 55 FOUNDATION Fieldbus Function matrix General layout of the function matrix The function matrix consists of four levels: Blocks -> Groups -> Function groups -> Functions 0000 0001 0002 0003 0009 … 0400...
  • Page 7: Codes Identifying Cells

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 2 Function matrix 2.1.5 Codes identifying cells Each cell (block, group, function group and function) in the function matrix has an individual, unique code. Blocks: The code is a letter (A, B, C, etc.) Groups: The code consists of three letters (AAA, ABA, BAA, etc.).
  • Page 8: Function Matrix

    2 Function matrix Device Functions Proline Promag 55 FOUNDATION Fieldbus Function matrix FUNCTION BLOCKS GROUPS GROUPS → → MEASURED VARIABLES MEASURING VALUES Page 10 → ( → Page 9) SYSTEM UNITS Page 11 ↓ → SPECIAL UNITS Page 14 →...
  • Page 9: Block Measured Variables

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 3 Block MEASURED VARIABLES Block MEASURED VARIABLES Endress+Hauser...
  • Page 10: Group Measuring Values

    3 Block MEASURED VARIABLES Device Functions Proline Promag 55 FOUNDATION Fieldbus Group MEASURING VALUES 3.1.1 Function group MAIN VALUES MEASURED ⇒ ⇒ MEASURING VALUES MAIN VALUES VARIABLES Function description → → MEASURED VARIABLES MEASURING VALUES MAIN VALUES Note! • The engineering units of all the measured variables shown here can be set in the SYSTEM UNITS group.
  • Page 11: Group System Units

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 3 Block MEASURED VARIABLES Group SYSTEM UNITS 3.2.1 Function group CONFIGURATION MEASURED ⇒ MEASURING VALUES VARIABLES ⇓ ⇒ SYSTEM UNITS CONFIGURATION Function description → → MEASURED VARIABLES SYSTEM UNITS CONFIGURATION You can select the units for measured variables in this function group.
  • Page 12 3 Block MEASURED VARIABLES Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → MEASURED VARIABLES SYSTEM UNITS CONFIGURATION UNIT VOLUME FLOW Use this function to select the unit for displaying the volume flow (volume/time). (0402) The unit you select here is also valid for: •...
  • Page 13: Function Group Additional Configuration

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 3 Block MEASURED VARIABLES 3.2.2 Function group ADDITIONAL CONFIGURATION MEASURED ⇒ MEASURING VALUES VARIABLES ⇓ ⇒ SYSTEM UNITS CONFIGURATION ⇓ ADDITIONAL CONF. Function description → → MEASURED VARIABLES SYSTEM UNITS ADDITIONAL CONFIGURATION UNIT DENSITY Use this function to select the unit for displaying the fluid density.
  • Page 14: Group Special Units

    3 Block MEASURED VARIABLES Device Functions Proline Promag 55 FOUNDATION Fieldbus Group SPECIAL UNITS 3.3.1 Function group DENSITY PARAMETER MEASURED ⇒ MEASURING VALUES VARIABLES ⇓ SYSTEM UNITS ⇓ ⇒ SPECIAL UNITS DENSITY PARAMETER Function description → → MEASURED VARIABLES SPECIAL UNITS DENSITY PARAMETER Use this function group to calculate a mass flow from a volume flow.
  • Page 15: Block Quick Setup

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 4 Block QUICK SETUP Block QUICK SETUP Function Block Group Functions groups QS COMMISS. T-DAT SAVE/LOAD QUICK SETUP ⇒ ⇒ ⇒ (1002) P. 15 (1009) P. 15 Function description QUICK SETUP QUICK SETUP Use this function to start the Setup menu for commissioning.
  • Page 16: Commissioning" Quick Setup Menu

    4 Block QUICK SETUP Device Functions Proline Promag 55 FOUNDATION Fieldbus "Commissioning" Quick Setup menu The "Commissioning" Quick Setup menu guides you systematically through all the important device functions that have to be configured for standard operation. XXX.XXX.XX HOME-POSITION Quick Setup...
  • Page 17 Device Functions Proline Promag 55 FOUNDATION Fieldbus 4 Block QUICK SETUP Note! • The display returns to the cell SETUP COMMISSIONING (1002) if you press the X key combination during parameter interrogation. The stored parameters remain valid. • The system units selected via the Quick Setup only apply for displaying on the local display and for parameters in the Transducer Blocks.
  • Page 18: Data Backup/Transmission

    • Duplicating data: current data are copied from an EEPROM to the T-DAT and then transferred to EEPROMs of identical measuring points. Note! Installing and removing T-DAT → See Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus. XXX.XXX.XX Quick Setup...
  • Page 19: Block User Interface

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE Block USER INTERFACE Endress+Hauser...
  • Page 20: Group Control

    • If you press the X key combination at startup, the language defaults to ENGLISH. • You can change the language group via the configuration program ToF Tool - Fieldtool Package. Please do not hesitate to contact your Endress+Hauser sales office if you have any questions.
  • Page 21 Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE Function description → → USER INTERFACE CONTROL BASIC CONFIGURATION CONTRAST LCD Use this function to optimize display contrast to suit local operating conditions. (2003) User input: 10 to 100%...
  • Page 22: Function Group Unlocking/Locking

    HOME position. You can also disable programming in this function by entering any number (other than the defined private code). • The Endress+Hauser service organization can be of assistance if you mislay your private code. DEFINE PRIVATE CODE...
  • Page 23: Function Group Operation

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE 5.1.3 Function group OPERATION ⇒ ⇒ USER INTERFACE CONTROL BASIC CONFIGURATION 200 ⇓ UNLOCKING/LOCKING 202 ⇓ OPERATION Function description → → USER INTERFACE CONTROL OPERATION TEST DISPLAY Use this function to test the operability of the local display and its pixels.
  • Page 24: Group Main Line

    5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus Group MAIN LINE 5.2.1 Function group CONFIGURATION ⇒ USER INTERFACE CONTROL ⇓ ⇒ MAIN LINE CONFIGURATION Function description → → USER INTERFACE MAIN LINE CONFIGURATION A0001253 1= main line, 2 = additional line, 3 = information line...
  • Page 25 Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE Function description → → USER INTERFACE MAIN LINE CONFIGURATION FORMAT Use this function to define the maximum number of places after the decimal point (2202) displayed for the reading in the main line.
  • Page 26: Function Group Multiplex

    5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus 5.2.2 Function group MULTIPLEX ⇒ USER INTERFACE CONTROL ⇓ ⇒ MAIN LINE CONFIGURATION ⇓ MULTIPLEX Function description → → USER INTERFACE MAIN LINE MULTIPLEX ASSIGN Use this function to define the second reading to be displayed in the main line alternately (2220) (every 10 seconds) with the value defined in the ASSIGN function (2200).
  • Page 27: Group Additional Line

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE Group ADDITIONAL LINE 5.3.1 Function group CONFIGURATION ⇒ USER INTERFACE CONTROL ⇓ MAIN LINE ⇓ ⇒ ADDITIONAL LINE CONFIGURATION Function description → → USER INTERFACE ADDITIONAL LINE CONFIGURATION A0001253...
  • Page 28 5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → USER INTERFACE ADDITIONAL LINE CONFIGURATION 100%-VALUE Note! (2401) This function is not available unless one of the following was selected in the ASSIGN function (2400): •...
  • Page 29: Function Group Multiplex

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE 5.3.2 Function group MULTIPLEX ⇒ USER INTERFACE CONTROL ⇓ MAIN LINE ⇓ ⇒ ADDITIONAL LINE CONFIGURATION ⇓ MULTIPLEX Function description → → USER INTERFACE ADDITIONAL LINE MULTIPLEX ASSIGN Use this function to define the second reading to be displayed in the additional line (2420) alternately (every 10 seconds) with the value defined in the function ASSIGN (2400).
  • Page 30 5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → USER INTERFACE ADDITIONAL LINE MULTIPLEX FORMAT Note! (2422) This function is not available unless a number was selected in the ASSIGN function (2420). Use this function to define the maximum number of places after the decimal point for the second value displayed in the additional line.
  • Page 31: Group Information Line

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE Group INFORMATION LINE 5.4.1 Function group CONFIGURATION ⇒ USER INTERFACE CONTROL ⇓ MAIN LINE ⇓ ADDITIONAL LINE ⇓ ⇒ INFORMATION LINE CONFIGURATION Function description → → USER INTERFACE INFORMATION LINE...
  • Page 32 5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → USER INTERFACE INFORMATION LINE CONFIGURATION 100%-VALUE Note! (2601) This function is not available unless one of the following was selected in the ASSIGN function (2600): •...
  • Page 33: Function Group Multiplex

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 5 Block USER INTERFACE 5.4.2 Function group MULTIPLEX ⇒ USER INTERFACE CONTROL ⇓ MAIN LINE ⇓ ADDITIONAL LINE ⇓ ⇒ INFORMATION LINE CONFIGURATION ⇓ MULTIPLEX Function description → → USER INTERFACE INFORMATION LINE...
  • Page 34 5 Block USER INTERFACE Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → USER INTERFACE INFORMATION LINE MULTIPLEX FORMAT Note! (2622) This function is not available unless a number was selected in the ASSIGN function (2600). Use this function to define the maximum number of places after the decimal point for the second value displayed in the information line.
  • Page 35: Block Totalizer

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 6 Block TOTALIZER Block TOTALIZER Endress+Hauser...
  • Page 36: Group Totalizer (1 To 3)

    6 Block TOTALIZER Device Functions Proline Promag 55 FOUNDATION Fieldbus Group TOTALIZER (1 to 3) 6.1.1 Function group CONFIGURATION ⇒ ⇒ TOTALIZER TOTALIZER 1 CONFIGURATION ⇓ ⇒ TOTALIZER 2 CONFIGURATION ⇓ ⇒ TOTALIZER 3 CONFIGURATION Function description → → TOTALIZER...
  • Page 37 Device Functions Proline Promag 55 FOUNDATION Fieldbus 6 Block TOTALIZER Function description → → TOTALIZER TOTALIZER (1 to 3) CONFIGURATION TOTALIZER MODE Use this function to define how the flow components are to be totalized. (3002) Options: BALANCE Positive and negative flow components. The positive and negative flow components are balanced.
  • Page 38: Function Group Operation

    6 Block TOTALIZER Device Functions Proline Promag 55 FOUNDATION Fieldbus 6.1.2 Function group OPERATION ⇒ ⇒ TOTALIZER TOTALIZER 1 CONFIGURATION ⇓ ⇓ OPERATION ⇒ TOTALIZER 2 CONFIGURATION ⇓ ⇓ OPERATION ⇒ TOTALIZER 3 CONFIGURATION ⇓ OPERATION Function description → →...
  • Page 39: Group Handling Totalizer

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 6 Block TOTALIZER Group HANDLING TOTALIZER ⇒ TOTALIZER TOTALIZER 1 ⇓ TOTALIZER 2 ⇓ TOTALIZER 3 ⇓ ⇒ HANDLING TOTALIZER DJA Handling totalizer functions Function description → → TOTALIZER HANDLING TOTALIZER Handling totalizer functions...
  • Page 40: Block Basic Function

    7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus Block BASIC FUNCTION Endress+Hauser...
  • Page 41: Group Foundation Fieldbus

    • The simulation mode is enabled and disabled by means of a jumper on the I/O board → see also Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus). • The status of the simulation mode is also shown in the parameter BLOCK_ERR of the Resource Block.
  • Page 42: Function Group Function Blocks

    7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus 7.1.2 Function group FUNCTION BLOCKS ⇒ ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GGA CONFIGURATION ⇓ FUNCTION BLOCKS Function description → → BASIC FUNCTION FOUNDATION FIELDBUS FUNCTION BLOCKS BLOCK SELECTION Use this function to select a function block whose value and status is shown in the (6220) subsequent functions.
  • Page 43: Function Group Information

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 7 Block BASIC FUNCTION 7.1.3 Function group INFORMATION ⇒ ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GGA CONFIGURATION ⇓ FUNCTION BLOCKS 6122 ⇓ INFORMATION Function description → → BASIC FUNCTION FOUNDATION FIELDBUS INFORMATION MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
  • Page 44: Group Process Parameter

    7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus Group PROCESS PARAMETER 7.2.1 Function group CONFIGURATION ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GAA ⇓ ⇒ PROCESS PARAMETER CONFIGURATION Function description → → BASIC FUNCTION PROCESS PARAMETER CONFIGURATION ASSIGN LOW FLOW CUT Use this function to assign the switch point for the low flow cut off.
  • Page 45 Device Functions Proline Promag 55 FOUNDATION Fieldbus 7 Block BASIC FUNCTION Function description → → BASIC FUNCTION PROCESS PARAMETER CONFIGURATION PRESSURE SHOCK The closure of a valve can cause brief but severe movements of the fluid in the piping SUPPRESSION system, movements which the measuring system registers.
  • Page 46: Function Group Epd Parameter

    7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus 7.2.2 Function group EPD PARAMETER ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GGA ⇓ ⇒ PROCESS PARAMETER CONFIGURATION ⇓ EPD PARAMETER Function description → → BASIC FUNCTION PROCESS PARAMETER EPD PARAMETER EMPTY PIPE DET.
  • Page 47 Device Functions Proline Promag 55 FOUNDATION Fieldbus 7 Block BASIC FUNCTION Function description → → BASIC FUNCTION PROCESS PARAMETER EPD PARAMETER EPD RESPONSE TIME Note! (6425) The function is only available if the function EMPTY PIPE DET. (6420) has been switched on.
  • Page 48: Function Group Adjustment

    7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus 7.2.3 Function group ADJUSTMENT ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GGA ⇓ ⇒ PROCESS PARAMETER CONFIGURATION ⇓ EPD PARAMETER ⇓ ADJUSTMENT Function description → → BASIC FUNCTION PROCESS PARAMETER ADJUSTMENT EPD ADJUSTMENT Use this function to activate the EPD adjustment for an empty or full measuring tube.
  • Page 49: Group System Parameter

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 7 Block BASIC FUNCTION Group SYSTEM PARAMETER 7.3.1 Function group CONFIGURATION ⇒ BASIC FUNCTION FOUNDATION FIELDBUS GGA ⇓ PROCESS PARAMETER ⇓ ⇒ SYSTEM PARAMETER CONFIGURATION Function description → → BASIC FUNCTION SYSTEM PARAMETER...
  • Page 50 7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → BASIC FUNCTION SYSTEM PARAMETER CONFIGURATION SPECIAL FILTER There is the option of activating two signal filters in this function. These filters make it (6606) possible to either suppress the signal caused by severely fluctuating flows (STANDARD option) or to reproduce it completely –...
  • Page 51: Group Sensor Data

    For this reason, the functions described below cannot be changed even when you enter your private code. Contact the Endress+Hauser service organization if you have any questions about these functions. K-FACTOR POSITIVE...
  • Page 52: Function Group Operation

    For this reason, the functions described below cannot be changed even when you enter your private code. Contact the Endress+Hauser service organization if you have any questions about these functions. MEASURING PERIOD Use this function to view the measuring period.
  • Page 53: Block Supervision

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 8 Block SUPERVISION Block SUPERVISION Endress+Hauser...
  • Page 54: Group System

    8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus Group SYSTEM 8.1.1 Function group CONFIGURATION ⇒ ⇒ SUPERVISION SYSTEM CONFIGURATION Function description → → SUPERVISION SYSTEM CONFIGURATION ALARM DELAY Use this function to define a time span in which the criteria for a fault have to be satisfied (8005) without interruption before a fault or notice message is generated.
  • Page 55: Function Group Operation

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 8 Block SUPERVISION 8.1.2 Function group OPERATION ⇒ ⇒ SUPERVISION SYSTEM CONFIGURATION ⇓ OPERATION Function description → → SUPERVISION SYSTEM OPERATION ACTUAL Use this function to check the present system condition. SYSTEM CONDITION...
  • Page 56 8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus Function description → → SUPERVISION SYSTEM OPERATION VALUE SIMULATION Note! MEASURAND The function is not visible unless the SIMULATION MEASURAND function (8043) is (8044) active. Use this function to specify a selectable value (e.g. 12 m /s).
  • Page 57: Group Version Info

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 8 Block SUPERVISION Group VERSION INFO 8.2.1 Function group DEVICE ⇒ SUPERVISION SYSTEM ⇓ ⇒ VERSION INFO DEVICE Function description → → SUPERVISION VERSION INFO DEVICE DEVICE SOFTWARE Use this function to view the current device software version.
  • Page 58: Function Group Amplifier

    • The language options of the available language group are displayed in the LANGUAGE (2000) function. • You can change the language group via the configuration program ToF Tool - Fieldtool Package. Please do not hesitate to contact your Endress+Hauser sales office if you have any questions. 8.2.4 Function group F-CHIP ⇒...
  • Page 59: Function Group I/O Module

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 8 Block SUPERVISION 8.2.5 Function group I/O MODULE ⇒ SUPERVISION SYSTEM ⇓ ⇒ VERSION INFO DEVICE ⇓ SENSOR ⇓ AMPLIFIER ⇓ F-CHIP ⇓ I/O MODULE Function description → → SUPERVISION VERSION INFO I/O MODULE...
  • Page 60 8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress+Hauser...
  • Page 61: Index Function Matrix

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 9 Index Function matrix Index Function matrix Blocks 822 = AMPLIFIER ......58 824 = F-CHIP .
  • Page 62 Device Functions Proline Promag 55 FOUNDATION Fieldbus 9 Index Function matrix 3040 = SUM ........38 3041 = OVERFLOW .
  • Page 63: Index (Local Operation)

    Device Functions Proline Promag 55 FOUNDATION Fieldbus 10 Index (local operation) Index (local operation) Actual system condition ......55 Damping Additional configuration (system units) .
  • Page 64 10 Index (local operation) Device Functions Proline Promag 55 FOUNDATION Fieldbus Configuration Multiplex ........33 Additional line .
  • Page 65 Device Functions Proline Promag 55 FOUNDATION Fieldbus 10 Index (local operation) Totalizer ........35 Configuration .
  • Page 66 10 Index (local operation) Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress+Hauser...
  • Page 67 Device Functions Proline Promag 55 FOUNDATION Fieldbus Table of contens (FOUNDATION Fieldbus) Table of contens (FOUNDATION Fieldbus) Operation via FOUNDATION Fieldbus 69 Additional function blocks..122 Block model ......69 Factory settings .
  • Page 68 Table of contens (FOUNDATION Fieldbus) Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress+Hauser...
  • Page 69 Device functions Proline Promag 55 FOUNDATION Fieldbus 1 Operation via FOUNDATION Fieldbus Operation via FOUNDATION Fieldbus Block model In the FOUNDATION Fieldbus all the device parameters are categorized according to their functional properties and task and are generally assigned to three different blocks. A block may be regarded as a container in which parameters and the associated functionalities are contained.
  • Page 70 1 Operation via FOUNDATION Fieldbus Device functions Proline Promag 55 FOUNDATION Fieldbus Transducer Analog Input Block Function Block FOUNDATION Fieldbus Discrete Output Block Resource Block Block ARITHMETIC Block INPUT Block SIGNAL Block INTEGRATOR Block A0006559-EN Fig. 1: Promag 55 FOUNDATION Fieldbus blocks The sensor signal is first prepared specifically for the flow in the measuring block (the Transducer Block).
  • Page 71 Device functions Proline Promag 55 FOUNDATION Fieldbus 2 Resource Block Resource Block A Resource Block contains all the data that uniquely identifies and characterizes the field device. It is an electronic version of a nameplate on the field device. Parameters of the Resource Block include device type, device name, manufacturer ID, serial number, etc.
  • Page 72 FOUNDATION Fieldbus I/O board (→ Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus, BA126D). The parameter WRITE_LOCK shows the status of the hardware write protection. The following statuses are possible: –...
  • Page 73 Device functions Proline Promag 55 FOUNDATION Fieldbus 2 Resource Block Parameters of the Resource Block The following table shows all the Endress+Hauser-specific parameters of the Resource Block. Note! FOUNDATION Fieldbus parameters are described in the "FOUNDATION Fieldbus Overview" Operating Instructions (BA013S) (available at: → www.endress.com → Download).
  • Page 74 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus Transducer Block The Transducer Blocks contain all the measurement- and device-specific parameters of the flowmeter. All the settings directly connected with the flow measurement/application are made here. They form the interface between the sensor-specific measured value preprocessing and the Analog Input function blocks required for automation.
  • Page 75 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block Signal processing The following figure shows the internal structure of the individual Transducer Blocks: Transducer Block “Flow” Simulation - Value Measurand Simulation - System Param. - Measurand Positive Zero Return...
  • Page 76 The primary functions and parameters of the Transducer Blocks are listed below. You will find an overview of all the available Endress+Hauser-specific parameters starting on → Page 78 ff. Important functions and parameters of the Transducer Blocks 3.2.1...
  • Page 77 In addition, the active device error is displayed via the "Diagnosis" Transducer Block in the "Diagnosis - Act.Sys. Condition" parameter ( → Page 90). For further information on rectifying errors → see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus (BA126D), "Troubleshooting" section.
  • Page 78 "Access - Code" parameter. Parameters of the "Flow" Transducer Block The following table shows all the Endress+Hauser-specific parameters of the "Flow" Transducer Block. These can only be changed after entering an enabling code in the "Access - Code" parameter. Note! FOUNDATION Fieldbus parameters are described in the "FOUNDATION Fieldbus Overview"...
  • Page 79 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) System Value - read only Use this parameter to view the current volume flow. Volume Flow The volume flow is made available as a process variable to the downstream Analog Input function blocks.
  • Page 80 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) System Unit - AUTO - OOS Use this parameter to select the unit for the mass flow (mass/time).
  • Page 81 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) System Unit - AUTO - OOS Use this parameter to select the unit for displaying the length of the Length nominal diameter.
  • Page 82 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) Sys. - Positive Zero AUTO - OOS Use this parameter to interrupt evaluation of measured variables. This is Return necessary when a piping system is being cleaned, for example.
  • Page 83 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) Low Flow Cut Off - AUTO - OOS Use this parameter to assign the switch point for the low flow cut off.
  • Page 84 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) Process - Pressure AUTO - OOS The closure of a valve can cause brief but severe movements of the fluid in Shock Suppression the piping system, movements which the measuring system registers.
  • Page 85 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) EPD - Adjustment AUTO - OOS Use this parameter to perform EPD adjustment for an empty or full measuring tube.
  • Page 86 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) EPD - Empty Pipe AUTO - OOS This status can be monitored at all times with the Empty Pipe Detection Detection function.
  • Page 87 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) EPD - Response AUTO - OOS Use this parameter to enter the time span in which the criteria for an...
  • Page 88 • The simulation acts independently of the position of the jumpers on the I/O board (→ see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus, BA126D). • The setting is not saved if the power supply fails.
  • Page 89 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Flow" Transducer Block/base index 1400 Write access with Parameter operating mode Description (MODE_BLK) Simulation - AUTO - OOS Use this parameter to specify a selectable value (e.g. 12 m³/s). This is used...
  • Page 90 Device functions Proline Promag 55 FOUNDATION Fieldbus Parameters of the "Diagnosis" Transducer Block The following table shows all the Endress+Hauser-specific parameters of the "Diagnosis" Transducer Block. These can only be changed after entering an enabling code in the "Access - Code" parameter.
  • Page 91 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Diagnosis" Transducer Block/base index 1600 Write access with Parameter operating mode Description (MODE_BLK) Sys. - Alarm Delay AUTO - OOS Use this parameter to define a time span in which the criteria for a fault have to be satisfied without interruption before a fault or notice message is generated.
  • Page 92 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Diagnosis" Transducer Block/base index 1600 Write access with Parameter operating mode Description (MODE_BLK) Sys. - AUTO - OOS Use this parameter to rectify errors occurring in the EEPROM. The Troubleshooting EEPROM is split into a number of blocks.
  • Page 93 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Diagnosis" Transducer Block/base index 1600 Write access with Parameter operating mode Description (MODE_BLK) Sys. - AUTO - OOS Use this parameter to save the parameter settings/configuration of the T-DAT Save/Load transmitter in a transmitter DAT (T-DAT), or to load the parameter settings from the T-DAT into the EEPROM (manual backup function).
  • Page 94 Device functions Proline Promag 55 FOUNDATION Fieldbus Parameters of the "Display" Transducer Block The following table shows all the Endress+Hauser-specific parameters of the "Display" Transducer Block. These can only be changed after entering an enabling code in the "Access - Code"...
  • Page 95 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Access - AUTO - OOS Use this function to specify a private code for enabling configuration. This Def.Private Code...
  • Page 96 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Config. - AUTO - OOS Use this parameter to enter a time constant defining how the display reacts...
  • Page 97 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) 1 = Main line 2 = Additional line 3 = Information line A0001253 Main Line - AUTO - OOS...
  • Page 98 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Main Line - AUTO - OOS Use this parameter to define the maximum number of places after the Format decimal point displayed for the reading in the main line.
  • Page 99 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Main Line Mux - AUTO - OOS Use this parameter to define the maximum number of places after the Format decimal point displayed for the reading in the main line.
  • Page 100 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Add. Line - AUTO - OOS Note! 100% - Value The entry is not active unless one of the following was selected in the parameter "Add.
  • Page 101 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Add. Line - AUTO - OOS Note! Display Mode The option is not active unless one of the following was selected in the parameter "Add.
  • Page 102 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Add. Line Mux - AUTO - OOS Note! 100%-Value The entry is not active unless one of the following was selected in the parameter "Add.
  • Page 103 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Add. Line Mux - AUTO - OOS Note! Display Mode The option is not active unless one of the following was selected in the parameter "Add.
  • Page 104 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Info Line - AUTO - OOS Note! 100%-Value The entry is not active unless one of the following was selected in the parameter "Info Line - Assign"...
  • Page 105 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Info Line - AUTO - OOS Note! Display Mode The option is not active unless one of the following was selected in the parameter "Info Line - Assign"...
  • Page 106 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Info Line Mux - AUTO - OOS Note! 100%-Value The entry is not active unless one of the following was selected in the parameter "Info Line Mux - Assign"...
  • Page 107 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Display" Transducer Block/base index 1800: Write access with Parameter operating mode Description (MODE_BLK) Info Line Mux - AUTO - OOS Note! Display Mode The option is not active unless one of the following was selected in the parameter "Info Line Mux - Assign"...
  • Page 108 Device functions Proline Promag 55 FOUNDATION Fieldbus Parameters of the "Totalizer" Transducer Block The following table shows all the Endress+Hauser-specific parameters of the "Totalizer" Transducer Block. These can only be changed after entering an enabling code in the "Access - Code"...
  • Page 109 Device functions Proline Promag 55 FOUNDATION Fieldbus 3 Transducer Block "Totalizer" Transducer Block/base index 1900: Write access with Parameter operating mode Description (MODE_BLK) Tot. 1 to 3 - Sum AUTO - OOS Use this parameter to view the total for the totalizer’s measured variable aggregated since measuring commenced.
  • Page 110 3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus "Totalizer" Transducer Block/base index 1900: Write access with Parameter operating mode Description (MODE_BLK) Tot. 1 to 3 - Mode AUTO - OOS Use this parameter to define how the flow components are to be totaled by the totalizer.
  • Page 111 Device functions Proline Promag 55 FOUNDATION Fieldbus 4 Function blocks Function blocks The function blocks contain the basic automation functions of the field device. We distinguish between different function blocks, e.g. Analog Input function block, PID function block (PID controller), etc.
  • Page 112 5 Analog Input function block Device functions Proline Promag 55 FOUNDATION Fieldbus Analog Input function block In the Analog Input function block (AI) the process variables from the Transducer Block are prepared for the subsequent automation functions (e.g. scaling, limit value processing). The automation function is defined by the connections of the outputs.
  • Page 113 The simulation mode is enabled by means of the corresponding jumpers on the I/O board (→ see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus, BA126D). The parameter L_TYPE is used to select the linearization type of the input or simulation value: •...
  • Page 114 5 Analog Input function block Device functions Proline Promag 55 FOUNDATION Fieldbus Important functions and parameters of the Analog Input function blocks The primary functions and parameters of the Analog Input function blocks are listed below. Note! All FOUNDATION Fieldbus parameters available are described in the "FOUNDATION Fieldbus Overview"...
  • Page 115 In the "Diagnosis" Transducer Block, the cause of the error message (notice/fault message) is displayed via the "Diag. - Act. Sys. Condition" parameter. A list of all the error messages, including remedial measures, is provided in the Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus (BA126D).
  • Page 116 5 Analog Input function block Device functions Proline Promag 55 FOUNDATION Fieldbus 5.2.6 Simulation of input/output Parameters of the Analog Input function block allow simulation of the input and output of the function block: Simulation of the input of the Analog Input function block: The parameter group SIMULATE can be used to specify the input value (measured value and status).
  • Page 117: Limit Values

    Device functions Proline Promag 55 FOUNDATION Fieldbus 5 Analog Input function block • OUT_SCALE parameter group OUT_SCALE 0 % OUT_SCALE 100% = 100 OUT_SCALE UNIT The result is that with an input value of, for example, 15 m /h a value of 50% is output via the parameter OUT.
  • Page 118 5 Analog Input function block Device functions Proline Promag 55 FOUNDATION Fieldbus Limit value process alarms If a limit value is infringed then the priority specified for the limit value alarm will be checked before the limit value violation is communicated to the fieldbus host system. The priority that specifies the action in the event of an active limit value violation is determined by the following parameters: –...
  • Page 119 Device functions Proline Promag 55 FOUNDATION Fieldbus 6 Discrete Output Function block Discrete Output Function block The Discrete Output function block (DO, Discrete Output) processes a discrete setpoint value received from an upstream function block or higher level process control system, with which various instrument functions (e.g.
  • Page 120 6 Discrete Output Function block Device functions Proline Promag 55 FOUNDATION Fieldbus In the AUTO operating mode (automatic operation), the set point value (parameter SP_D) is prescribed directly in the Discrete Output function block. In this case, the parameter CAS_IN_D is not taken into consideration in the internal calculation.
  • Page 121 Device functions Proline Promag 55 FOUNDATION Fieldbus 6 Discrete Output Function block 6.2.4 Values for the parameters CAS_IN_D, RCAS_IN_D, OUT_D, and SP_D Via the Discrete Output function block, different instrument functions in the Transducer Block can be initiated via manufacturer-specific, fixed set point values from an upstream function block.
  • Page 122 7 Additional function blocks Device functions Proline Promag 55 FOUNDATION Fieldbus Additional function blocks Note! Other function blocks such as the PID, Arithmetic, Input Selector, Signal Characterizer and Integrator function block are described in the "FOUNDATION Fieldbus Overview" (BA013S) Operating Instructions (available at: → www.endress.com → Download).
  • Page 123: Factory Settings

    Device functions Proline Promag 55 FOUNDATION Fieldbus 8 Factory settings Factory settings SI units (not for USA and Canada) Low flow cut off, full scale value Nominal diameter Low flow cut off Full scale value (approx. v = 0.04 m/s) (approx.
  • Page 124 8 Factory settings Device functions Proline Promag 55 FOUNDATION Fieldbus Country Language Poland Polish Portugal Portuguese Russia Russian Singapore English South Africa English Spain Espanol Sweden Svenska Switzerland Deutsch Thailand English Density, length, temperature Unit Density kg/l Length Temperature ° C...
  • Page 125 Device Functions Proline Promag 55 FOUNDATION Fieldbus Index (FOUNDATION Fieldbus) Block model ........69...
  • Page 126 Temperature ....... 124 Fault message See Operating Instructions for Proline Promag 55 FOUN- Main Line - ...
  • Page 127 Notice message Sensor - HW-Rev.Number See Operating Instructions for Proline Promag 55 FOUN- “Flow” Transducer Block ..... . 89 DATION FIELDBUS (BA026D) Sensor - Prod.Number...
  • Page 128 Device Functions Proline Promag 55 FOUNDATION Fieldbus Sys. - CIP Samples Tot. 1 to 3 - Sum “Flow” Transducer Block ..... . 82 “Totalizer”...
  • Page 129 Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress+Hauser...
  • Page 130 www.endress.com/worldwide BA127D/06/en/09.06 71032705 FM+SGML 6.0...

Table of Contents