Device Functions Proline Promag 55 FOUNDATION Fieldbus
Endress+Hauser
4

Block QUICK SETUP

Block
Group
QUICK SETUP
(B)
QUICK SETUP
Use this function to start the Setup menu for commissioning.
COMMISSIONING
(1002)
Options:
YES
NO
Factory setting:
NO
!
You will find a flowchart of the COMMISSIONING Setup menu on Page 16.
For more detailed information on Setup menus, please refer to the Operating Instructions
for Proline Promag 55 FOUNDATION FIELDBUS.
T-DAT SAVE/LOAD
Use this function to save the parameter settings / configuration of the transmitter in a
(1009)
transmitter DAT (T-DAT), or to load the parameter settings from the T-DAT into the
EEPROM (manual security function).
Application examples:
• After commissioning, the actual measuring point parameters can be saved to the
• If the transmitter is replaced for some reason, the data from the T-DAT can be loaded
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT into EEPROM)
Factory setting:
CANCEL
!
• If the target device has an older software version, the message "TRANSM. SW-DAT" is
• LOAD
• SAVE
Function
groups
QS COMMISS.
(1002) P. 15
Function description
QUICK SETUP
Note!
T-DAT as a backup.
into the new transmitter (EEPROM).
Note!
displayed during startup. Then only the SAVE option is available.
This option is only possible if:
– The target device has the same software version as, or a more recent software
version than, the source device or
– The T-DAT contains valid data that can be retrieved
This option is always available.
4 Block QUICK SETUP
Functions
T-DAT SAVE/LOAD
(1009) P. 15
15