Group Foundation Fieldbus; Function Group Configuration - Endress+Hauser Proline Promag 55 Operating Manual

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

Device Functions Proline Promag 55 FOUNDATION Fieldbus
Endress+Hauser
7.1

Group FOUNDATION FIELDBUS

7.1.1

Function group CONFIGURATION

BASIC FUNCTION
G
BASIC FUNCTION
WRITE PROTECT
Use this function to check whether the measuring device can be write-accessed via the
(6200)
fieldbus.
User interface:
OFF
ON
Factory setting:
OFF
!
Hardware write protection is activated and deactivated by means of a jumper on the I/O
board (
SIMULATION
Use this function to check whether a simulation in the Analog Input or Discrete Output
(6201)
function block is possible.
User interface:
OFF
possible.
ON
Factory setting:
ON
!
• The simulation mode is enabled and disabled by means of a jumper on the I/O board
• The status of the simulation mode is also shown in the parameter BLOCK_ERR of the
DEVICE PD-TAG
Use this function to enter a tag name for the measuring device.
(6203)
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:
E+H_PROMAG_55_XXXXXXXXXXX
FOUNDATION FIELDBUS GGA
Function description
FOUNDATION FIELDBUS
Write access via FOUNDATION Fieldbus possible
Write access via FOUNDATION Fieldbus not possible
Note!
see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
Simulation in the Analog Input and Discrete Output function block is not
Simulation in the Analog Input and Discrete Output function block is possible
Note!
(
see also Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
Resource Block.
7 Block BASIC FUNCTION
CONFIGURATION
CONFIGURATION
620
41