Endress+Hauser Proline Promag 55 Operating Manual page 50

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

7 Block BASIC FUNCTION
50
BASIC FUNCTION
SPECIAL FILTER
There is the option of activating two signal filters in this function. These filters make it
(6606)
possible to either suppress the signal caused by severely fluctuating flows (STANDARD
option) or to reproduce it completely – both on the display and on the FOUNDATION
Fieldbus output (DYNAMIC FLOW option).
Options:
STANDARD
For signal output with normal, stable flow.
DYNAMIC FLOW
For signal output with severely fluctuating or pulsating flow.
Factory setting:
STANDARD
"
• The signal behavior at the outputs also depends on the SYSTEM DAMPING (6603)
• Additional filter settings (e.g. STANDARD CIP or DYNAMIC FLOW CIP) can only be
Device Functions Proline Promag 55 FOUNDATION Fieldbus
Function description
SYSTEM PARAMETER
Caution!
function.
selected using a special service code. Such settings that are mostly made by a service
technician are deleted again if the customer code is entered anew and can then no
longer be activated.