Group Measuring Values; Function Group Main Values - Endress+Hauser Proline Promag 55 Operating Manual

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

3 Block MEASURED VARIABLES
10
3.1

Group MEASURING VALUES

3.1.1

Function group MAIN VALUES

MEASURED
A
VARIABLES
MEASURED VARIABLES
!
Note!
• The engineering units of all the measured variables shown here can be set in the SYSTEM UNITS group.
• If the fluid in the pipe flows backwards, a negative sign prefixes the flow reading on the display.
CALCULATED MASS
Use this function to view the calculated mass flow. The mass flow is derived from the
FLOW
measured volume flow and the fixed (or temperature compensated) density.
(0000)
User interface:
5-digit floating-point number, including unit and sign
(e.g. 462.87 kg/h; –731.63 lb/min; etc.)
VOLUME FLOW
Use this function to view the actual measured volume flow.
(0001)
User interface:
5-digit floating-point number, including unit and sign
(e.g. 5.5445 dm
DENSITY
Displays the fixed density.
(0005)
User interface:
5-digit floating-point number, including unit (corresponding to 0.10000 to
6.0000 kg/dm
e.g. 1.2345 kg/dm
Device Functions Proline Promag 55 FOUNDATION Fieldbus
MEASURING VALUES
AAA
Function description
MEASURING VALUES
3
3
/min; 1.4359 m
/h; –731.63 gal/d; etc.)
3
)
3
3
; 993.5 kg/m
; 1.0015 SG_20 °C; etc.
MAIN VALUES
MAIN VALUES
Endress+Hauser