6 Block TOTALIZER
38
6.1.2
Function group OPERATION
⇒
TOTALIZER
D
The function descriptions below apply to Totalizers 1 to 3; the Totalizers are independently configurable.
SUM
Use this function to view the total for the totalizer's measured variable aggregated since
(3040)
measuring commenced. The value can be positive or negative, depending on the setting
selected in the "TOTALIZER MODE" function (3002), and the direction of flow.
User interface:
Max. 7-digit floating-point number, including sign and unit
(e.g. 15467.04 m
!
• The effect of the setting in the "TOTALIZER MODE" function ( → Page 37) is as
• The totalizer's response to faults is defined in the "FAILSAFE ALL TOT" function
OVERFLOW
Use this function to view the overflow for the totalizer aggregated since measuring
(3041)
commenced.
Total flow quantity is represented by a floating-point number consisting of max. 7 digits.
You can use this function to view higher numerical values (> 9,999,999) as overflows.
The effective quantity is thus the total of OVERFLOW plus the value returned by the
SUM function.
Example:
Reading for 2 overflows: 2
The value displayed in the function SUM = 196845.7 dm
Effective total quantity = 20196845.7 dm
User interface:
Integer with exponent, including sign and unit, e.g. 2
Device Functions Proline Promag 55 FOUNDATION Fieldbus
TOTALIZER 1
⇓
TOTALIZER 2
⇓
TOTALIZER 3
Function description
→
TOTALIZER
TOTALIZER (1 to 3)
3
; –4925.631 kg)
Note!
follows:
– If the setting is "BALANCE", the totalizer balances flow in the positive and negative
directions.
– If the setting is "FORWARD", the totalizer registers only flow in the positive
direction.
– If the setting is "REVERSE", the totalizer registers only flow in the negative
direction.
(3801), ( → Page 39).
⋅
7
10
dm
⇒
DAA
CONFIGURATION
⇓
OPERATION
⇒
DAB
CONFIGURATION
⇓
OPERATION
⇒
DAC
CONFIGURATION
⇓
OPERATION
→
OPERATION
3
3
(= 20000000 dm
)
3
3
⋅
7
3
10
dm