Group System; Function Group Configuration - Endress+Hauser Proline Promag 55 Operating Manual

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

8 Block SUPERVISION
54
8.1

Group SYSTEM

8.1.1

Function group CONFIGURATION

SUPERVISION
J
ALARM DELAY
Use this function to define a time span in which the criteria for a fault have to be satisfied
(8005)
without interruption before a fault or notice message is generated.
Depending on the setting and the type of fault, this suppression acts on:
• Display
• Output blocks (AI Blocks) FOUNDATION Fieldbus interface
User input:
0 to 100 s (in steps of one second)
Factory setting:
0 s
"
If this function is activated, fault and notice messages are delayed by the time
corresponding to the setting before being transmitted to the higher-order controller
(process controller, etc.). It is therefore imperative to check in advance in order to make
sure whether a delay of this nature could affect the safety requirements of the process. If
fault and notice messages may not be suppressed, a value of 0 seconds must be entered
here.
PERMANENT STORAGE
This function displays whether permanent saving of all parameters in the EEPROM is
(8007)
switched on or off.
User interface:
OFF
ON
Factory setting:
ON
Device Functions Proline Promag 55 FOUNDATION Fieldbus
SYSTEM
Function description
SUPERVISION
SYSTEM
CONFIGURATION
Caution!
JAA
CONFIGURATION
Endress+Hauser
800