Endress+Hauser Proline Promag 55 Operating Manual page 110

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

3 Transducer Block
110
Write access with
Parameter
operating mode
(MODE_BLK)
Tot. 1 to 3 - Mode
AUTO - OOS
Tot. 1 to 3 - Reset
AUTO - OOS
Tot. - Reset All
AUTO - OOS
Tot. - Failsafe All
AUTO - OOS
Device functions Proline Promag 55 FOUNDATION Fieldbus
"Totalizer" Transducer Block/base index 1900:
Use this parameter to define how the flow components are to be totaled by
the totalizer.
Options:
BALANCE
Positive and negative flow components. The positive and negative flow
components are balanced. In other words, net flow in the flow direction is
registered.
FORWARD
Positive flow components only
REVERSE
Negative flow components only
Factory setting:
Totalizer 1 = BALANCE
Totalizer 2 = FORWARD
Totalizer 3 = REVERSE
Resets the totalizer "Tot. 1 to 3 - Sum" parameter to zero.
Options:
NO
YES
Factory setting:
NO
!
Note!
Totalizer resetting can also be controlled or triggered by means of cyclic
data transfer via the Discrete Output function block.
Resets all totalizers "Tot. 1 to 3 - Sum" parameter simultaneously to zero.
Options:
NO
YES
Factory setting:
NO
!
Note!
Totalizer resetting can also be controlled or triggered by means of cyclic
data transfer via the Discrete Output function block.
Use this parameter to define the common response of all Totalizers (1 to 3)
in case of error.
Options
STOP → The totalizers are paused until the fault is rectified.
ACTUAL VALUE → The totalizers continue to count based on the actual
flow measured value. The fault is ignored .
HOLD VALUE → The totalizers continue to count the flow based on the
last valid flow value (before the fault occurred).
Factory setting:
STOP
Description
Endress+Hauser