Function Group Multiplex - Endress+Hauser Proline Promag 55 Operating Manual

Foundation fieldbus electromagnetic flow measuring system description of device functions
Hide thumbs Also See for Proline Promag 55:
Table of Contents

Advertisement

5 Block USER INTERFACE
26
5.2.2

Function group MULTIPLEX

USER INTERFACE
C
ASSIGN
Use this function to define the second reading to be displayed in the main line alternately
(2220)
(every 10 seconds) with the value defined in the ASSIGN function (2200).
Options:
OFF
VOLUME FLOW
MASS FLOW
VOLUME FLOW IN %
MASS FLOW IN %
TOTALIZER (1 to 3)
AI1 - OUT VALUE
AI2 - OUT VALUE
AI3 - OUT VALUE
AI4 - OUT VALUE
AI5 - OUT VALUE
PID - IN VALUE (controlled variable)
PID - CAS IN VALUE (external set point)
PID - OUT VALUE (manipulated variable)
Factory setting:
OFF
100%-VALUE
!
(2221)
This function is only available if VOLUME FLOW IN % or MASS FLOW IN % was
selected in the function ASSIGN (2220).
Use this function to define the flow value to be shown on the display as the 100% value.
User input:
5-digit floating-point number
Factory setting:
Nominal diameter and country dependent → Page 123 ff.
FORMAT
Use this function to define the maximum number of places after the decimal point for the
(2222)
second value displayed in the main line.
Options:
XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting:
X.XXXX
!
• Note that this setting only affects the reading as it appears on the display, it has no
• The places after the decimal point as computed by the measuring device cannot always
Device Functions Proline Promag 55 FOUNDATION Fieldbus
CONTROL
MAIN LINE
Function description
USER INTERFACE
MAIN LINE
Note!
Note!
influence on the accuracy of the system's calculations.
be displayed, depending on this setting and the engineering unit. In these instances an
arrow appears on the display between the measured value and the engineering unit
(e.g. 1.2 → kg/h), indicating that the measuring system is computing with more
decimal places than can be shown on the display.
CAA
CCA
CONFIGURATION
MULTIPLEX
MULTIPLEX
Endress+Hauser
220
222

Advertisement

Table of Contents
loading

Table of Contents