3. SIGNALS AND WIRING
(f) Ready-off command from controller
It is the same as (1) (f) in this section.

3.11 Grounding

WARNING
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt
and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to "EMC Installation Guidelines".
MCCB
(Note)
Power
supply
Note. For the power supply specifications, refer to section 1.3.
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal
(marked
) of the servo amplifier to the protective earth (PE) of the cabinet.
Cabinet
Protective earth (PE)
Servo amplifier
CN2
MC
L1
L2
L3
L11
L21
U
V
W
CN1A
Outer
box
3 - 46
Servo motor
Encoder
U
M
V
W
Ensure to connect the wire to the
PE terminal of the servo amplifier.
Do not connect the wire directly to
the grounding of the cabinet.