APPENDIX
(2) MR-J4-200B-RJ to MR-J4-22KB-RJ
MCCB
3-phase or 1-phase
200 V AC to 240 V AC
(Note 2) Forced stop 2
Note 1. For the power supply specifications, refer to section 1.3.
2. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.8.3.
3. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less (160 ms or less for 5 kW or more). Depending on the main circuit voltage and operation pattern, bus
voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic
brake deceleration is not required, delay the time to turn off the magnetic contactor.
4. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
5. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
6. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
can be configured by one.
7. Driving the on switch and off switch with the DC power supply meets IEC/EN 60204-1 requirements.
8. Do not use the 24 V DC interface power supply for the magnetic contactor DC power supply. Always use the power supply
designed exclusively for the magnetic contactor.
9. If disabling ALM (Malfunction) output with the parameter, configure the power supply circuit which switches off the magnetic
contactor after detection of alarm occurrence on the servo system controller side.
10. When wires used for L11 and L21 are thinner than wires used for L1/L2/L3 and N-, use a fuse. (Refer to app. 15.4.)
App. 15.2 Power supply capacity
The power supply capacity is the same as that for the AC power supply input. Refer to section 10.2 for
details.
Malfunction
RA1
Emergency stop switch
(Note 1)
24 V DC (Note 7, 8)
MC (Note 3)
+
AC/DC
Converter
(283 V DC to
-
340 V DC)
(Note 10)
(Note 4)
Main circuit power supply
24 V DC (Note 6)
(Note 5)
Short-circuit connector
(packed with the servo
amplifier)
App. - 69
OFF
ON
MC
Servo amplifier
L1
L2
L3
N-
L11
L21
CN3
CN3
24 V DC (Note 6)
EM2
DOCOM
ALM
DOCOM
CN8
MC
SK
(Note 2)
Malfunction
RA1
(Note 9)