11. OPTIONS AND PERIPHERAL EQUIPMENT
(3) MR-J4-11KA(-RJ) to MR-J4-22KA(-RJ)/MR-J4-11KA4(-RJ) to MR-J4-22KA4(-RJ) (when using the
supplied regenerative resistor)
CAUTION
When using the regenerative resistors supplied to the servo amplifier, the specified number of resistors
(4 or 5 resistors) must be connected in series. If they are connected in parallel or in less than the
specified number, the servo amplifier may become faulty and/or the regenerative resistors burn.
Install the resistors at intervals of about 70 mm. Cooling the resistors with two cooling fans (1.0 m
or more, 92 mm × 92 mm) improves the regeneration capability. In this case, set "_ _ F A" in [Pr. PA02].
Servo amplifier
Regenerative resistor
MR-J4-11KA(-RJ)
GRZG400-0.8Ω
MR-J4-15KA(-RJ)
GRZG400-0.6Ω
MR-J4-22KA(-RJ)
GRZG400-0.5Ω
MR-J4-11KA4(-RJ)
GRZG400-2.5Ω
MR-J4-15KA4(-RJ)
MR-J4-22KA4(-RJ)
Note. The following shows an indication example of symbol.
The regenerative resistor supplied with 11 kW to 22 kW servo amplifiers does not
have a protective cover. Touching the resistor (including wiring/screw hole area)
may cause a burn injury and electric shock. Even if the power was shut-off, be
careful until the bus voltage discharged and the temperature decreased because
of the following reasons.
It may cause a burn injury due to very high temperature without cooling.
It may cause an electric shock due to charged capacitor of the servo amplifier.
Do not use servo amplifiers with external regenerative resistors other than the
combinations specified below. Otherwise, it may cause a fire.
5 m or shorter
(Note)
Series connection
Cooling fan
Note. The number of resistors connected in series depends on the resistor type. The
thermal sensor is not mounted on the attached regenerative resistor. An abnormal
heating of resistor may be generated at a regenerative circuit failure. Install a thermal
sensor near the resistor and establish a protective circuit to shut off the main circuit
power supply when abnormal heating occurs. The detection level of the thermal
sensor varies according to the settings of the resistor. Set the thermal sensor in the
most appropriate position on your design basis, or use the thermal sensor built-in
regenerative option. (MR-RB5R, MR-RB9F, MR-RB9T, MR-RB5K-4, or MR-RB6K-4)
Symbol (Note)
GR400 R80K
GR400 R60K
GR400 R50K
GR400 2R5K
GRZG400-2Ω
GR400 2R0K
Servo amplifier
P+
C
Regenerative power [W]
Normal
500
850
500
850
Symbol
GR400 R80K
Regenerative resistor
11 - 16
Resultant
resistance [Ω]
Cooling
800
3.2
3
1300
2.5
800
10
1300
10
3
/min
Number of
resistors
4
5
4
5