Settings; Information List; Power System Data 2; Description - Siemens SIPROTEC 7SJ62 Manual

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

2.1.5.3 Settings

Addr.
Parameter
302
CHANGE

2.1.5.4 Information List

No.
Information
-
GroupA act
-
GroupB act
-
GroupC act
-
GroupD act
7
>Set Group Bit0
8
>Set Group Bit1
2.1.6

Power System Data 2

2.1.6.1 Description

The general protection data (P.System Data 2) include settings associated with all functions rather than a
specific protection or monitoring function. In contrast to the P.System Data 1 as discussed before, they can
be changed with the setting group.
Applications
When the primary reference voltage and the primary reference current of the protected object are set, the
device is able to calculate and output the operational measured value percentage.
For purposes of fault location, a maximum of three different line sections can be considered.
For utilization in motors, detection of the motor start represents an important feature. Exceeding a configured
current value serves as a criterion.
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Setting Options
Group A
Group B
Group C
Group D
Binary Input
Protocol
Type of In-
formation
IntSP
Setting Group A is active
IntSP
Setting Group B is active
IntSP
Setting Group C is active
IntSP
Setting Group D is active
SP
>Setting Group Select Bit 0
SP
>Setting Group Select Bit 1
Default Setting
Group A
Change to Another Setting Group
Comments
Functions
2.1 General
Comments
55