Functions
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Addr.
Parameter
3108
64-1 VGND
3109
64-1 VGND
3110
64-1 VGND
3111
T-DELAY Pickup
3112
64-1 DELAY
3113
50Ns-2 PICKUP
3113
50Ns-2 PICKUP
3114
50Ns-2 DELAY
3115
67Ns-2 DIRECT
3117
50Ns-1 PICKUP
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3119
51Ns PICKUP
3119
51Ns PICKUP
3120
51NsTIME DIAL
3121A
50Ns T DROP-OUT
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
3126
RESET DELAY
3127
51Ns I T min
3127
51Ns I T min
240
C
Setting Options
1.8 .. 200.0 V; ∞
1.8 .. 170.0 V; ∞
10.0 .. 225.0 V; ∞
0.04 .. 320.00 sec; ∞
0.10 .. 40000.00 sec; ∞
0.001 .. 1.500 A
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
0.00 .. 320.00 sec; ∞
Forward
Reverse
Non-Directional
0.001 .. 1.500 A
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
0.00 .. 320.00 sec; ∞
0.001 .. 1.400 A
0.003 .. 0.500 A
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.10 .. 4.00 sec; ∞
0.00 .. 60.00 sec
Forward
Reverse
Non-Directional
0.001 .. 1.200 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
-45.0 .. 45.0 °
COS ϕ
SIN ϕ
0 .. 60 sec
0.003 .. 1.400 A
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Default Setting
40.0 V
64-1 Ground Displace-
ment Voltage
40.0 V
64-1 Ground Displace-
ment Voltage
70.0 V
64-1 Ground Displace-
ment Voltage
1.00 sec
Time-DELAY Pickup
10.00 sec
64-1 Time Delay
0.300 A
50Ns-2 Pickup
10.00 A
50Ns-2 Pickup
50.00 A
1.00 sec
50Ns-2 Time Delay
Forward
67Ns-2 Direction
0.100 A
50Ns-1 Pickup
2.00 A
50Ns-1 Pickup
10.00 A
2.00 sec
50Ns-1 Time delay
0.100 A
51Ns Pickup
0.004 A
51Ns Pickup
1.00 A
51Ns Pickup
5.00 A
1.00 sec
51Ns Time Dial
0.00 sec
50Ns Drop-Out Time
Delay
Forward
67Ns-1 Direction
0.010 A
Release directional
element
0.50 A
Release directional
element
2.50 A
0.0 °
Correction Angle for Dir.
Determination
COS ϕ
Measurement method for
Direction
1 sec
Reset Delay
1.333 A
51Ns Current at const.
Time Delay T min
15.00 A
51Ns Current at const.
Time Delay T min
75.00 A
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008