Siemens SIPROTEC 7SJ62 Manual page 42

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Functions
2.1 General
No.
Information
67
Resume
68
Clock SyncError
69
DayLightSavTime
70
Settings Calc.
71
Settings Check
72
Level-2 change
73
Local change
110
Event Lost
113
Flag Lost
125
Chatter ON
140
Error Sum Alarm
144
Error 5V
145
Error 0V
146
Error -5V
147
Error PwrSupply
160
Alarm Sum Event
177
Fail Battery
178
I/O-Board error
181
Error A/D-conv.
183
Error Board 1
184
Error Board 2
185
Error Board 3
186
Error Board 4
187
Error Board 5
188
Error Board 6
189
Error Board 7
191
Error Offset
192
Error1A/5Awrong
193
Alarm NO calibr
194
Error neutralCT
220
CT Ph wrong
301
Pow.Sys.Flt.
302
Fault Event
303
sens Gnd flt
320
Warn Mem. Data
321
Warn Mem. Para.
322
Warn Mem. Oper.
323
Warn Mem. New
502
Relay Drop Out
510
Relay CLOSE
545
PU Time
546
TRIP Time
42
Type of In-
formation
OUT
Resume
OUT
Clock Synchronization Error
OUT
Daylight Saving Time
OUT
Setting calculation is running
OUT
Settings Check
OUT
Level-2 change
OUT
Local setting change
OUT_Ev
Event lost
OUT
Flag Lost
OUT
Chatter ON
OUT
Error with a summary alarm
OUT
Error 5V
OUT
Error 0V
OUT
Error -5V
OUT
Error Power Supply
OUT
Alarm Summary Event
OUT
Failure: Battery empty
OUT
I/O-Board Error
OUT
Error: A/D converter
OUT
Error Board 1
OUT
Error Board 2
OUT
Error Board 3
OUT
Error Board 4
OUT
Error Board 5
OUT
Error Board 6
OUT
Error Board 7
OUT
Error: Offset
OUT
Error:1A/5Ajumper different from setting
OUT
Alarm: NO calibration data available
OUT
Error: Neutral CT different from MLFB
OUT
Error: Range CT Ph wrong
OUT
Power System fault
OUT
Fault Event
OUT
sensitive Ground fault
OUT
Warn: Limit of Memory Data exceeded
OUT
Warn: Limit of Memory Parameter exceeded
OUT
Warn: Limit of Memory Operation exceeded
OUT
Warn: Limit of Memory New exceeded
SP
Relay Drop Out
SP
General CLOSE of relay
VI
Time from Pickup to drop out
VI
Time from Pickup to TRIP
Comments
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008

Advertisement

Table of Contents
loading

Table of Contents