Siemens SIPROTEC 7SJ62 Manual page 408

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
Power Supply
Table 3-7
Jumper
X51
X52
X53
Pickup Voltages of BI1 to BI3
Table 3-8
Binary inputs
BI1
BI2
BI3
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115/230 VAC
Contact Mode for Binary Outputs BO1 and BO2
Table 3-9
for
Jumper
BO1
BO2
408
Jumper settings for the nominal voltage of the integrated power supply on the processor board
A–CPU as from 7SJ62.../FF
24/48 VDC
not used
not used
not used
not changeable
Jumper settings for the pickup voltages of the binary inputs BI1 to BI3 on the processor board
A–CPU as from 7SJ62.../FF
Jumper
X21
X22
X23
Jumper settings for the contact mode of relays BO1 and BO3 on the processor board A–CPU
as from 7SJ62.../FF
Open in quiescent state
(NO)
X41
1-2
X42
1-2
Rated Voltage
60 to 125 VDC
1-2
1-2 and 3-4
1-2
interchangeable
1)
19 VDC threshold
88 VDC threshold
L
L
L
Closed in quiescent state
(NC)
2-3
2-3
C53000-G1140-C207-2, Release date 01.2008
110 to 250 VDC,
115 to 230 VAC
2-3
2-3
2-3
2)
176 VDC threshold
M
H
M
H
M
H
Presetting
1-2
1-2
SIPROTEC, 7SJ62/64, Manual

Advertisement

Table of Contents
loading

Table of Contents