Siemens SIPROTEC 7SJ62 Manual page 235

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Table 2-15
MofPU = 1 to 1.94
1,00
1,50
1,06
1,56
1,13
1,63
1,19
1,69
1,25
1,75
1,31
1,81
1,38
1,88
1,44
1,94
Figure 2-91
Determination of Ground-Faulted Phase
The ground-faulted phase may be identified in an ungrounded or resonant-grounded system, if the device is
supplied by three voltage transformers connected in a grounded-wye configuration. The phase in which the
voltage lies below setting VPH MIN at address 3106 is identified as the faulty phase as long as the other two
phase voltages simultaneously exceed the setting VPH MAX at address 3107. The setting VPH MIN must be
set less than the minimum expected operational phase-to-ground voltage. A typical setting for this address
would be 40 V. Setting VPH MAX must be greater than the maximum expected operational phase-to-ground
voltage, but less than the minimum expected operational phase-to-phase voltage. For V
mately 75 V is a typical setting. These settings have no significance in a grounded system.
Displacement Voltage Element V
The displacement voltage 64-1 VGND (address 3108 or 3109) or 64-1 VGND (address 3110) is used to pick
up ground fault detection. At the same time, pickup of the voltage element is a condition for initiation of direction
determination (when setting the direction characteristic to cos ϕ / sin ϕ ). If the direction characteristic is
set to V0/I0 ϕ mea., the displacement voltage element is not relying on the current elements at all. Depend-
ing on the configuration at address 213 VT Connect. 3ph, only the applicable limit value at address 3108
64-1 VGND, 3109 64-1 VGND or 3110 64-1 VGND is accessible.
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Preferential Values of Standardized Currents for User-specific Tripping Curves
MofPU = 2 to 4.75
2,00
3,50
2,25
3,75
2,50
4,00
2,75
4,25
3,00
4,50
3,25
4,75
Use of a user-defined characteristic
0
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
MofPU = 5 to 7.75
5,00
6,50
8,00
5,25
6,75
9,00
5,50
7,00
10,00
5,75
7,25
11,00
6,00
7,50
12,00
6,25
7,75
13,00
14,00
Functions
MofPU p = 8 to 20
15,00
16,00
17,00
18,00
19,00
20,00
= 100 V, approxi-
Nom
235

Advertisement

Table of Contents
loading

Table of Contents