Addr.
Parameter
1308
51N TIME DIAL
1309
51N TIME DIAL
1310
51N Drop-out
1311
51N IEC CURVE
1312
51N ANSI CURVE
1313A
MANUAL CLOSE
1314A
50N-2 active
1315A
50N T DROP-OUT
1316A
50N-3 active
1317
50N-3 PICKUP
1318
50N-3 DELAY
1319A
50N-3 measurem.
1320A
50N-2 measurem.
1321A
50N-1 measurem.
1322A
51N measurem.
1330
50N/51N
1331
MofPU Res T/TEp
1501
FCT 67/67-TOC
1502
67-2 PICKUP
1503
67-2 DELAY
1504
67-1 PICKUP
1505
67-1 DELAY
1507
67-TOC PICKUP
1508
67 TIME DIAL
1509
67 TIME DIAL
1510
67-TOC Drop-out
1511
67- IEC CURVE
1512
67- ANSI CURVE
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Function
C
Setting Options
0.05 .. 3.20 sec; ∞
50/51 Overcur.
0.50 .. 15.00 ; ∞
50/51 Overcur.
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
50N-3 instant.
50N-2 instant.
50N-1 instant.
51N instant.
Inactive
50/51 Overcur.
Always
With 79 Active
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
with 79 active
0.25 .. 35.00 A; ∞
50/51 Overcur.
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
1.00 .. 20.00 I/Ip; ∞
50/51 Overcur.
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
50/51 Overcur.
0.01 .. 999.00 TD
67 Direct. O/C
OFF
ON
0.10 .. 35.00 A; ∞
67 Direct. O/C
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
67 Direct. O/C
0.10 .. 35.00 A; ∞
67 Direct. O/C
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
67 Direct. O/C
67 Direct. O/C
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
67 Direct. O/C
0.50 .. 15.00 ; ∞
67 Direct. O/C
67 Direct. O/C
Instantaneous
Disk Emulation
67 Direct. O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
67 Direct. O/C
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
0.20 sec
51N Time Dial
5.00
51N Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50N-2 instant.
Manual Close Mode
Always
50N-2 active
0.00 sec
50N Drop-Out Time Delay
Always
50N-3 active
∞ A
50N-3 Pickup
0.00 sec
50N-3 Time Delay
Fundamental
50N-3 measurement of
Fundamental
50N-2 measurement of
Fundamental
50N-1 measurement of
Fundamental
51N measurement of
50N/51N
Multiple of Pickup <-> T/TEp
OFF
67, 67-TOC Phase Time Over-
current
2.00 A
67-2 Pickup
10.00 A
0.10 sec
67-2 Time Delay
1.00 A
67-1 Pickup
5.00 A
0.50 sec
67-1Time Delay
1.00 A
67-TOC Pickup
5.00 A
0.50 sec
67-TOC Time Dial
5.00
67-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
Appendix
A.8 Settings
Comments