Siemens SIPROTEC 7SJ62 Manual page 641

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Addr.
Parameter
6024
S3: x'
6025
S3: Line angle
6026
S3: line length
6027
S3: Line length
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A
Direct CO
6111A
TSUP VOLTAGE
6112
T-SYN. DURATION
6113A
25 Synchron
6120
T-CB close
6121
Balancing V1/V2
6122A
ANGLE ADJUSTM.
6123
CONNECTIONof V2
6125
VT Vn2, primary
6130
dV ASYN V2>V1
6131
dV ASYN V2<V1
6132
df ASYN f2>f1
6133
df ASYN f2<f1
6140
SYNC PERMIS.
6141
F SYNCHRON
6142
dV SYNC V2>V1
6143
dV SYNC V2<V1
dα SYNC α2> α1
6144
dα SYNC α2< α1
6145
6146
T SYNC-DELAY
6150
dV SYNCHK V2>V1
6151
dV SYNCHK V2<V1
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Function
C
Setting Options
0.0050 .. 9.5000 Ω/km
P.System Data 2
1A
0.0010 .. 1.9000 Ω/km
5A
P.System Data 2
10 .. 89 °
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
0.1 .. 1000.0 km
SYNC function 1
ON
OFF
SYNC function 1
(Setting options depend
on configuration)
SYNC function 1
20 .. 125 V
SYNC function 1
20 .. 140 V
SYNC function 1
1 .. 60 V
SYNC function 1
20 .. 140 V
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
SYNC function 1
SYNC function 1
YES
NO
SYNC function 1
0.01 .. 0.60 sec
SYNC function 1
0.50 .. 2.00
SYNC function 1
0 .. 360 °
SYNC function 1
A-G
B-G
C-G
A-B
B-C
C-A
SYNC function 1
0.10 .. 800.00 kV
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.01 .. 2.00 Hz
SYNC function 1
0.01 .. 2.00 Hz
SYNC function 1
YES
NO
SYNC function 1
0.01 .. 0.04 Hz
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
2 .. 80 °
SYNC function 1
2 .. 80 °
SYNC function 1
0.00 .. 60.00 sec
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
Default Setting
0.1500 Ω/km
S3: feeder reactance per km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: line length in miles
100.0 km
S3: Line length in kilometer
OFF
Synchronizing Function
None
Synchronizable circuit breaker
90 V
Minimum voltage limit: Vmin
110 V
Maximum voltage limit: Vmax
5 V
Threshold V1, V2 without voltage
80 V
Threshold V1, V2 with voltage
NO
ON-Command at V1< and V2>
NO
ON-Command at V1> and V2<
NO
ON-Command at V1< and V2<
NO
Direct ON-Command
0.10 sec
Supervision time of V1>;V2> or
V1<;V2<
30.00 sec
Maximum duration of Synchroni-
zation
YES
Switching at synchronous condi-
tion
0.06 sec
Closing (operating) time of CB
1.00
Balancing factor V1/V2
0 °
Angle adjustment (transformer)
A-B
Connection of V2
12.00 kV
VT nominal voltage V2, primary
2.0 V
Maximum voltage difference
V2>V1
2.0 V
Maximum voltage difference
V2<V1
0.10 Hz
Maximum frequency difference
f2>f1
0.10 Hz
Maximum frequency difference
f2<f1
YES
Switching at synchronous condi-
tions
0.01 Hz
Frequency threshold ASYN <-->
SYN
5.0 V
Maximum voltage difference
V2>V1
5.0 V
Maximum voltage difference
V2<V1
10 °
Maximum angle difference
alpha2>alpha1
10 °
Maximum angle difference
alpha2<alpha1
0.00 sec
Release delay at synchronous
conditions
5.0 V
Maximum voltage difference
V2>V1
5.0 V
Maximum voltage difference
V2<V1
Appendix
A.8 Settings