Setting Notes - Siemens SIPROTEC 7SJ62 Manual

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Functions
2.9 Frequency Protection 81 O/U
2.9.2

Setting Notes

General
Frequency protection is only in effect and accessible if address 154 81 O/U is set to Enabled during config-
uration of protective functions. If the fuction is not required Disabled is set. The function can be turned ON or
OFF under address 5401 FCT 81 O/U.
By setting the parameters 5421 bis 5424, the function of each of the elements 81-1 PICKUP to 81-4 PICKUP
is set individually as overfrequency or underfrequency protection or set to OFF, if the element is not required.
Minimum Voltage
Address 5402 Vmin is used to set the minimum voltage. Frequency protection is blocked as soon as the
minimum voltage is undershot.
On all three-phase connections and single-phase connections of a phase-to-phase voltage, the threshold must
be set as a phase-to-phase value. With a single-phase phase-to-ground connection the threshold is set as a
phase-to-ground voltage.
Pickup Values
The setting as overfrequency or underfrequency element does not depend on the parameterization of the
threshold values of the respective element. An element can also function, for example, as an overfrequency
element if its threshold value is set below the nominal frequency and vice versa.
If frequency protection is used for load shedding purposes, the setting values depend on the actual power
system conditions. Normally, a graded load shedding is required that takes into account the importance of the
consumers or consumer groups.
Further application examples exist in the field of power stations. Here too, the frequency values to be set mainly
depend on the specifications of the power system / power station operator. The underfrequency protection safe-
guards the power station's own demand by disconnecting it from the power system on time. The turbo governor
regulates the machine set to the nominal speed. Consequently, the station's own demands can be continuously
supplied at nominal frequency.
Under the assumption that the apparent power is reduced by the same degree, turbine-driven generators can,
as a rule, be continuously operated down to 95% of the nominal frequency. However, for inductive consumers,
the frequency reduction not only means an increased current input, but also endangers stable operation. For
this reason, only a short-term frequency reduction down to about 48 Hz (for f
is permissible.
A frequency increase can, for example, occur due to a load shedding or malfunction of the speed regulation
(e.g. in an island network). In this way, the frequency increase protection can, for example, be used as over-
speed protection.
Dropout Thresholds
The dropout threshold is defined via the adjustable dropout-difference address 5415 DO differential. It
can thus be adjusted to the network conditions. The dropout difference is the absolute-value difference
between pickup threshold and dropout threshold. The default value of 0.02 Hz can usually remain. Should,
however, frequent minor frequency fluctuations be expected, this value should be increased.
Time Delays
The delay times 81-1 DELAY to 81-4 DELAY (addresses 5405, 5408, 5411 and 5414) allow the frequency
elements to be graded, e.g. for load shedding equipment. The set times are additional delay times not including
the operating times (measuring time, dropout time) of the protection function.
184
= 50 Hz) or 58 Hz (for f
N
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
= 60 Hz)
N