Appendix
A.8 Settings
Addr.
Parameter
7151
50N-1
7152
50-2
7153
50N-2
7154
51
7155
51N
7156
67-1
7157
67N-1
7158
67-2
7159
67N-2
7160
67 TOC
7161
67N TOC
7162
sens Ground Flt
7163
46
7164
BINARY INPUT
7165
3Pol.PICKUP BLK
7166
50-3
7167
50N-3
7200
bef.1.Cy:50-1
7201
bef.1.Cy:50N-1
7202
bef.1.Cy:50-2
7203
bef.1.Cy:50N-2
7204
bef.1.Cy:51
7205
bef.1.Cy:51N
646
Function
C
Setting Options
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
YES
NO
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
Default Setting
No influence
50N-1
No influence
50-2
No influence
50N-2
No influence
51
No influence
51N
No influence
67-1
No influence
67N-1
No influence
67-2
No influence
67N-2
No influence
67 TOC
No influence
67N TOC
No influence
(Sensitive) Ground Fault
No influence
46
No influence
Binary Input
NO
3 Pole Pickup blocks 79
No influence
50-3
No influence
50N-3
Set value T=T
before 1. Cycle: 50-1
Set value T=T
before 1. Cycle: 50N-1
Set value T=T
before 1. Cycle: 50-2
Set value T=T
before 1. Cycle: 50N-2
Set value T=T
before 1. Cycle: 51
Set value T=T
before 1. Cycle: 51N
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008