Further Information
The following instruction should be noted:
• As the power factor does not differentiate between capacitive and inductive, the sign of the reactive power
may be used with CFC-help as an additional criterion.
2.17.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
VOLTAGE
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
C
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binary Input
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Exceeding
Dropping below
Ia
Ib
Ic
In
In sensitive
In2
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
2.17 Flexible Protection Functions
Default Setting
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured
Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Ia
Current
Please select
Voltage
Functions
Comments
293