Information List - Siemens SIPROTEC 7SJ62 Manual

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Addr.
Parameter
6015
S2: Line angle
6016
S2: line length
6017
S2: Line length
6021
S3: RE/RL
6022
S3: XE/XL
6023
S3: x'
6024
S3: x'
6025
S3: Line angle
6026
S3: line length
6027
S3: Line length

2.1.6.4 Information List

No.
Information
126
ProtON/OFF
356
>Manual Close
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
4602
>52-b
16019
>52 Wear start
16020
52 WearSet.fail
16027
52WL.blk I PErr
16028
52WL.blk n PErr
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
C
Setting Options
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
0.0050 .. 15.0000 Ω/mi
1A
0.0010 .. 3.0000 Ω/mi
5A
0.0050 .. 9.5000 Ω/km
1A
0.0010 .. 1.9000 Ω/km
5A
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
Type of In-
formation
IntSP
Protection ON/OFF (via system port)
SP
>Manual close signal
OUT
Relay PICKUP
OUT
Relay GENERAL TRIP command
VI
Primary fault current Ia
VI
Primary fault current Ib
VI
Primary fault current Ic
OUT
Manual close signal detected
SP
>Enable 50/67-(N)-2 (override 79 blk)
SP
>52-a contact (OPEN, if bkr is open)
SP
>52-b contact (OPEN, if bkr is closed)
SP
>52 Breaker Wear Start Criteria
OUT
52 Wear blocked by Time Setting Failure
OUT
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
OUT
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
Default Setting
85 °
S2: Line angle
62.1 Miles
S2: line length in miles
100.0 km
S2: Line length in kilome-
ter
1.00
S3: Zero seq. compensat-
ing factor RE/RL
1.00
S3: Zero seq. compensat-
ing factor XE/XL
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S3: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: line length in miles
100.0 km
S3: Line length in kilome-
ter
Comments
Functions
2.1 General
Comments
61