Addr.
Parameter
3120
51NsTIME DIAL
3121A
50Ns T DROP-OUT
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
3126
RESET DELAY
3127
51Ns I T min
3127
51Ns I T min
3128
51Ns I T knee
3128
51Ns I T knee
3129
51Ns T knee
3130
PU CRITERIA
3131
M.of PU TD
3132
51Ns TD
3140
51Ns Tmin
3140
51Ns T min
3141
51Ns Tmax
3141
51Ns T max
3142
51Ns TIME DIAL
3143
51Ns Startpoint
3150
50Ns-2 Vmin
3150
50Ns-2 Vmin
3150
50Ns-2 Vmin
3151
50Ns-2 Phi
3152
50Ns-2 DeltaPhi
3153
50Ns-1 Vmin
3153
50Ns-1 Vmin
3153
50Ns-1 Vmin
3154
50Ns-1 Phi
3155
50Ns-1 DeltaPhi
3301
INTERM.EF
3302
Iie>
3302
Iie>
3302
Iie>
3303
T-det.ext.
3304
T-sum det.
3305
T-reset
3306
Nos.det.
4001
FCT 46
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Function
C
Setting Options
0.10 .. 4.00 sec; ∞
Sens. Gnd Fault
Sens. Gnd Fault
0.00 .. 60.00 sec
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Sens. Gnd Fault
0.001 .. 1.200 A
Sens. Gnd Fault
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
Sens. Gnd Fault
-45.0 .. 45.0 °
COS ϕ
Sens. Gnd Fault
SIN ϕ
Sens. Gnd Fault
0 .. 60 sec
Sens. Gnd Fault
0.003 .. 1.400 A
Sens. Gnd Fault
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Sens. Gnd Fault
0.003 .. 0.650 A
Sens. Gnd Fault
1A
0.05 .. 17.00 A
5A
0.25 .. 85.00 A
Sens. Gnd Fault
0.20 .. 100.00 sec
Sens. Gnd Fault
Vgnd OR INs
Vgnd AND INs
1.00 .. 20.00 MofPU; ∞
Sens. Gnd Fault
0.01 .. 999.00 TD
Sens. Gnd Fault
0.05 .. 1.50
Sens. Gnd Fault
0.00 .. 30.00 sec
Sens. Gnd Fault
0.10 .. 30.00 sec
Sens. Gnd Fault
0.00 .. 30.00 sec
Sens. Gnd Fault
0.50 .. 200.00 sec
0.05 .. 15.00 sec; ∞
Sens. Gnd Fault
Sens. Gnd Fault
1.0 .. 4.0
Sens. Gnd Fault
0.4 .. 50.0 V
Sens. Gnd Fault
1.8 .. 50.0 V
Sens. Gnd Fault
10.0 .. 90.0 V
Sens. Gnd Fault
-180.0 .. 180.0 °
Sens. Gnd Fault
0.0 .. 180.0 °
Sens. Gnd Fault
0.4 .. 50.0 V
Sens. Gnd Fault
1.8 .. 50.0 V
Sens. Gnd Fault
10.0 .. 90.0 V
Sens. Gnd Fault
-180.0 .. 180.0 °
Sens. Gnd Fault
0.0 .. 180.0 °
Intermit. EF
OFF
ON
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
0.005 .. 1.500 A
Intermit. EF
0.00 .. 10.00 sec
Intermit. EF
0.00 .. 100.00 sec
Intermit. EF
1 .. 600 sec
Intermit. EF
2 .. 10
46 Negative Seq
OFF
ON
Default Setting
1.00 sec
51Ns Time Dial
0.00 sec
50Ns Drop-Out Time Delay
Forward
67Ns-1 Direction
0.010 A
Release directional element
0.50 A
Release directional element
2.50 A
0.0 °
Correction Angle for Dir. Deter-
mination
COS ϕ
Measurement method for Direc-
tion
1 sec
Reset Delay
1.333 A
51Ns Current at const. Time
Delay T min
15.00 A
51Ns Current at const. Time
Delay T min
75.00 A
0.040 A
51Ns Current at Knee Point
5.00 A
51Ns Current at Knee Point
25.00 A
23.60 sec
51Ns Time Delay at Knee Point
Vgnd OR INs
Sensitive Ground Fault PICKUP
criteria
Multiples of PU
0.20
51Ns Time Dial
1.20 sec
51Ns Minimum Time Delay
0.80 sec
51Ns Minimum Time Delay
5.80 sec
51Ns Maximum Time Delay
93.00 sec
51Ns Maximum Time Delay (at
51Ns PU)
1.35 sec
51Ns Time Dial
1.1
51Ns Start Point of Inverse
Charac.
2.0 V
50Ns-2 minimum voltage
2.0 V
50Ns-2 minimum voltage
10.0 V
50Ns-2 minimum voltage
-90.0 °
50Ns-2 angle phi
30.0 °
50Ns-2 angle delta phi
6.0 V
50Ns-1 minimum voltage
6.0 V
50Ns-1 minimum voltage
15.0 V
50Ns-1 minimum voltage
-160.0 °
50Ns-1 angle phi
100.0 °
50Ns-1 angle delta phi
OFF
Intermittent earth fault protection
1.00 A
Pick-up value of interm. E/F
stage
5.00 A
1.00 A
Pick-up value of interm. E/F
stage
5.00 A
1.000 A
Pick-up value of interm. E/F
stage
0.10 sec
Detection extension time
20.00 sec
Sum of detection times
300 sec
Reset time
3
No. of det. for start of int. E/F prot
OFF
46 Negative Sequence Protec-
tion
Appendix
A.8 Settings
Comments
Time-Dial
637