Siemens SIPROTEC 7SJ62 Manual page 630

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
0
T TRIP DELAY
0A
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLK.by Vol.Loss
0A
DROPOUT RATIO
0A
DROPOUT RATIO
0A
DO differential
201
CT Starpoint
202
Vnom PRIMARY
203
Vnom SECONDARY
204
CT PRIMARY
205
CT SECONDARY
206A
Vph / Vdelta
209
PHASE SEQ.
210A
TMin TRIP CMD
211A
TMax CLOSE CMD
212
BkrClosed I MIN
213
VT Connect. 3ph
214
Rated Frequency
215
Distance Unit
217
Ignd-CT PRIM
218
Ignd-CT SEC
235A
ATEX100
238
Ignd2-CT PRIM
240
VT Connect. 1ph
250A
50/51 2-ph prot
251A
CT Connect.
260
Ir-52
261
OP.CYCLES AT Ir
262
Isc-52
263
OP.CYCLES Isc
264
Ix EXPONENT
265
Cmd.via control
266
T 52 BREAKTIME
630
Function
C
Setting Options
Flx
0.00 .. 3600.00 sec
Flx
0.00 .. 60.00 sec
Flx
0.00 .. 60.00 sec
Flx
NO
YES
Flx
0.70 .. 0.99
Flx
1.01 .. 3.00
Flx
0.02 .. 1.00 Hz
P.System Data 1
towards Line
towards Busbar
P.System Data 1
0.10 .. 800.00 kV
P.System Data 1
100 .. 225 V
P.System Data 1
10 .. 50000 A
P.System Data 1
1A
5A
P.System Data 1
0.10 .. 3.00
P.System Data 1
A B C
A C B
P.System Data 1
0.01 .. 32.00 sec
P.System Data 1
0.01 .. 32.00 sec
P.System Data 1
1A
0.04 .. 1.00 A
5A
0.20 .. 5.00 A
P.System Data 1
Van, Vbn, Vcn
Vab, Vbc, VGnd
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
P.System Data 1
50 Hz
60 Hz
P.System Data 1
km
Miles
P.System Data 1
1 .. 50000 A
P.System Data 1
1A
5A
P.System Data 1
NO
YES
P.System Data 1
1 .. 50000 A
P.System Data 1
NO
Van
Vbn
Vcn
Vab
Vbc
Vca
P.System Data 1
ON
OFF
P.System Data 1
A, B, C, (Gnd)
A,G2,C,G; G->B
A,G2,C,G; G2->B
P.System Data 1
10 .. 50000 A
P.System Data 1
100 .. 1000000
P.System Data 1
10 .. 100000 A
P.System Data 1
1 .. 1000
P.System Data 1
1.0 .. 3.0
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
1 .. 600 ms
Default Setting
1.00 sec
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
YES
Block in case of Meas.-Voltage
Loss
0.95
Dropout Ratio
1.05
Dropout Ratio
0.02 Hz
Dropout differential
towards Line
CT Starpoint
12.00 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
100 A
CT Rated Primary Current
1A
CT Rated Secondary Current
1.73
Matching ratio Phase-VT To
Open-Delta-VT
A B C
Phase Sequence
0.15 sec
Minimum TRIP Command Dura-
tion
1.00 sec
Maximum Close Command Du-
ration
0.04 A
Closed Breaker Min. Current
Threshold
0.20 A
Van, Vbn, Vcn
VT Connection, three-phase
50 Hz
Rated Frequency
km
Distance measurement unit
60 A
Ignd-CT rated primary current
1A
Ignd-CT rated secondary current
NO
Storage of th. Replicas w/o
Power Supply
60 A
Ignd2-CT rated primary c. (conn.
to I2)
NO
VT Connection, single-phase
OFF
50, 51 Time Overcurrent with
2ph. prot.
A, B, C, (Gnd)
CT Connection
125 A
Rated Normal Current (52 Break-
er)
10000
Switching Cycles at Rated
Normal Current
25000 A
Rated Short-Circuit Breaking
Current
50
Switch. Cycles at Rated Short-
Cir. Curr.
2.0
Exponent for the Ix-Method
None
52 B.Wear: Open Cmd. via
Control Device
80 ms
Breaktime (52 Breaker)
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Comments